Software user manual – SurgeX EV-23010 User Manual
Page 13
![background image](/manuals/742460/13/background.png)
Software User Manual
•
Twelve types of events are logged:
Overload: Load current draw has exceeded 25A
Surge: enVision has been exposed to a transient voltage
in one of the 3 possible modes (between Live and
Neutral, between Live and Ground, between Neutral and
Ground) with a peak amplitude of 500V* or higher and a
frequency of 20 kHz or higher. *500V surge voltage
amplitude applies to IEEE C62.41 Category B Impulse;
surge voltage amplitudes necessary for detection of other
surge types may vary.
Over Voltage (Cutoff): Line voltage exceeded the over
voltage shutdown threshold, and connected equipment
was turned off.
Over Voltage (Record): Line voltage exceeded the over
voltage record threshold, and connected equipment was
not turned off.
Under Voltage (Record): Line voltage dropped below the
under voltage record threshold, and connected equipment
was not turned off.
Under Voltage (Cutoff): Line voltage dropped below the
under voltage shutdown threshold, and connected
equipment was turned off.
Power Outage: Loss of AC power.
Turn On: The enVision outlets were turned on.
Turn Off (Cycle): A power cycle was initiated by a
received command.
Turn Off (Software): Outlets were turned off by a received
command.
Turn Off (Button): Outlets were turned off by the
pushbuttons.
Turn Off (Loss of Ground): Outlets were turned off due to
the loss of the safety ground conductor at the wall
receptacle.