5.7 Self-Test Failure Shut Down

The SEQ circuitry has integral self-monitoring which tells the microprocessor that the surge protection is on-line

and operating within specification. This menu item allows an option to be selected so that the unit will begin the

power down sequence should the self-test ever fail.

Menu Item

Options

Description

Self-Test Shut

Down

Disable

Banks will not be powered off if self-test fails

Enable

Banks will be powered off if self-test fails

5.8 Restore Functions

There are two menu items which, when enabled, allow the SEQ to restore the original “on” condition after shut-

down caused either by loss of AC power (or out-of-range AC) or by an over-ride. When these options are

disabled, the SEQ will not power up when the condition that caused the shut down goes away. The restore

functions cannot be used in conjunction with applied voltage or latching type remote control inputs.

Menu Item

Options

Description

Power Fail

Restore

Disable

Banks will remain off after a power failure

Enable

Restore the original status after a power failure

Over-Ride

Restore

Disable

Original status will not be restored after an over-ride

Enable

Original status will be restored after an over-ride

5.9 Password

A password can be set which will prevent unauthorized access to the programming mode. From one to six letters,

A through Z, can be used as a password.

It is important to remember the password because, once it has been set, you cannot get into the

programming mode again without entering the password. If you do forget the password, the only way to

erase it is to erase all the set-up information. If you ever need to do this, please call the factory to obtain

instructions.

When you select Password in the menu you will see a blinking cursor on the bottom line of the display. Set the

first letter of the password by turning ADJ. Then advance SEL one click so that the cursor moves to the next

position and repeat the process until you have set all the letters of your chosen password.

To erase a password set the cursor on the first letter and turn ADJ counter-clockwise until you see only the cursor

and no letter above it. Then turn SEL one click back. It is not necessary to erase each letter; erasing the first letter

erases the whole password.

Menu Item

Options

Description

Password

A - Z

Set optional password of up to six letters. Set each letter with ADJ

and advance SEL to go to the next letter.