SYMPTOM

POSSIBLE CAUSE

CHECK THIS...

CORRECTIVE ACTION

No visual signal
or electronic
output on optional
transmitter

Float is stuck or
damaged

Remove float and
inspect

Clean or replace
float as necessary

Some flipper
indicators do not
flip over

Flags are stuck

Check flag assembly

Open the flipper
assembly cover
and clean all flags

Flipper indication
varies but no
4-20mA output
from optional
transmitter

PCB failure

Check transmitter
PCB for proper
connections and
operation

Rewire or replace
PCB

No output from
optional transmitter

Incorrectly wired

Check wiring
matches
instructions
provided

Rewire transmitter
as required

Incorrect supply
voltage

Provide 15 to 30
VDC power at
terminals

Check power
supply and wiring

Troubleshooting