Fault Conditions

Linear = mm/inches

Drawing 0091140

Dimensions are for

reference only.

Contact the factory

for certified drawings

for a particular model

number.

14685 West 105th Street, Lenexa, KS 66215

 913-888-2630  800-676-6794 USA  Fax 913-888-0767

Registered Quality System to ISO 9001

Printed in USA

www.sorinc.com

If a malfunction occurs which is traced to the transmitter, it should be removed for
inspection and tested. If the transmitter has been subjected to excess pressure,
vibration, shock or extreme supply voltage (as in the case of a lightning strike),
damage may be indicated by a constant output, irrespective of the applied pressure.
Overpressure may also cause high or unstable readings.

Blocked pressure ports or pipes may cause a similar symptom and should be rectified
before carrying out further tests.

The transmitter can withstand pressure of 150% of its rated range without calibration
change. Pressures above this may cause irreparable damage. Frequent causes of such
overpressures are high transient pressures, which may not be easy to detect during
normal operation.