Calibration

 Factory Preset units have been set at the SOR factory to customer specifications and

are tamper-proof. The set point is locked and sealed. It cannot be changed in the field.
TP accessory designator indicates factory preset.

 Field Adjustable units have a recessed Allen screw for set point adjustment. Remove

knurled cap and adjust the set point as follows:

Use 1/8” hex Allen wrench to turn adjusting screw to achieve desired set point.

Turn adjusting screw clockwise (in) to increase set point.

Turn adjusting screw counterclockwise (out) to decrease set point.

Use an external pressure measuring device to accurately calibrate set points.

NOTE: SOR discourages fi eld modifi cations, change-out of wetted parts, or repair. It is
preferred that products be returned to SOR for inspection or repair. Contact the factory for
return authorization. Field repair should be performed by qualifi ed instrument technicians
with adherence to SOR procedures.