Maximum Recommended Spans between Arched Supports
According to radius of curve and load for two sides clamped glazing.
Structure
Thickness
Sheet curvature
radius
Recommended (center-to-center) Distance between Supporting arches
according to wind/Snow loads below
50 Kg/m²
10 psf
80 Kg/m²
16 psf
100 Kg/m²
20 psf
120 Kg/m²
24.6 psf
mm
mm
Inch
mm
Inch
mm
Inch
mm
Inch
mm
Inch
Twin Wall
6
1050
41
2000
79
1730
68
1420
56
1020
40
1500
59
1470
58
1090
43
890
35
660
26
1800
71
1140
45
860
34
690
27
580
23
2200
88
810
32
690
27
-
-
-
-
2800
110
500
20
350
14
-
-
-
-
4000
158
500
20
350
14
-
-
-
-
6000
236
500
20
350
14
-
-
-
-
8
1400
55
1650
65
1450
57
1320
52
1170
46
1800
71
1420
56
1270
50
1070
42
890
35
2200
88
1090
43
890
35
710
28
600
24
2800
110
840
33
620
19
450
18
-
-
4000
158
600
24
500
19
-
-
-
-
6000
236
570
23
480
19
-
-
-
-
10
1750
69
1630
68
1420
56
1170
46
1020
40
2200
88
1320
52
960
38
810
32
660
26
2800
110
890
35
650
26
600
24
550
22
4000
158
750
29
550
22
500
20
450
18
6000
236
700
27
520
21
500
20
420
18
Triple Wall
8
1760
70
1320
52
1170
46
980
39
750
30
2200
87
1025
41
780
31
580
23
520
21
2800
110
750
30
570
23
400
16
-
-
4000
158
500
20
450
18
-
-
-
-
6000
236
480
19
400
16
-
-
-
-
10
2200
88
1220
48
880
35
720
29
580
23
2800
110
780
31
580
23
500
20
450
18
4000
158
620
25
500
20
450
18
400
16
6000
236
550
22
450
18
400
16
-
-
16
2800
118
1850
73
1650
65
1450
57
1200
48
4000
158
1450
57
1220
48
940
37
850
34
6000
236
1050
42
1000
40
850
34
800
32
X-Lite
16
3000
120
1750
69
1600
63
1500
59
1400
55
5000
200
1350
53
1200
47
1100
43
1000
39
25
5000
197
1650
64
1450
57
1400
55
1350
53
6000
236
1550
61
1350
53
1300
51
1250
49
32
6400
252
1650
64
1550
61
1350
53
1300
51
8000
315
1550
61
1450
57
1250
49
1200
47
35
7000
276
1650
65
1550
61
1350
53
1300
51
8200
322
1550
61
1450
57
1250
49
1200
47
Notes:
1. A hyphen sign in the table (-) means that the sheet cannot be used at the relevant range.
2. Generally a span of less than 600 mm (24 in.) is impractical for this installation configuration.
3. The lowest radius that appears in the upper row of every sheet group in the table is the minimum permitted cold bending radius for that specific sheet type.