beautypg.com

4 battery protection – OPTI-UPS MD120L User Manual

Page 84

background image

Chapter 2 Operations 27

27

2.4 Battery Protection

The following functions should be fitted by commissioning engineers with specified software.

1.

Battery Low Pre-warning

The battery under voltage pre-warning occurs before the end of discharge. After this pre-warning,

the battery should have the capacity for 3 remaining minutes discharging with full load. The time is user

configured from 3 to 60 minutes.

2.

Battery discharge (EOD)off protection

If the battery voltage is lower than the EOD, the battery converter will be shut down. EOD is

adjustable from 1.6V to 1.75V per cell (VRLA) or 0.9 to 1.1 V per cell (NiCd)

3.

Battery Circuit Breaker (BCB) Alarm

The alarm occurs when the battery disconnect device disconnects. The external battery connects to

the UPS through the external battery circuit breaker. The circuit breaker is manually closed and tripped

by the UPS control circuit.

This manual is related to the following products: