3.2.1 Normal Module Start

This procedure must be followed when turning on the UPS from a fully powered down condition.

The operating procedures are as follows:

警告

危 险

Warning

This procedure results in mains voltage being applied to the UPS output terminals. If any load

equipment is connected to the UPS output terminals please check with the load user that it is safe to

apply power. If the load is not ready to receive power then ensure that it is safely to close the output

switch of external distribution cabinet.

1. Close UPS output switch and input switch in turns.

The LCD starts up at this time. The Rectifier indicator flashes during the startup of rectifier. The

rectifier enters normal operation state, and after about 30s, the rectifier indicator goes steady green. After

initialization, the bypass static switch closes. The UPS Mimic LEDs will indicate as shown in table 3-1:

Table 3-1 Indicator status

LED

Status

Rectifier indicator

Green

Battery indicator

Red

Bypass indicator

Green

Inverter indicator

Off

Load indicator

Green

Status indicator

Green

警告

危 险

Note

The output circuit breaker must be closed first, followed by input circuit breaker, or the rectifier cannot
be started, and alarm “rectifier failure”.

The inverter starts up at this time, the inverter indicator flashes. After the rectifier enters normal

operation state, UPS power supply will transfer from bypass to inverter, then the bypass indicator turns

off, and load indicator lights. The status of indicators is shown in table 3-2.

Table 3-2 Indicator Status

LED

Status

Rectifier indicator

Green

Battery indicator

Red

Bypass indicator

Off

Inverter indicator

Green

Load indicator

Green

Status indicator

Green

2. Close external battery switch, battery indicator turns off, a few minutes later, the battery will be

charged by UPS which will enter normal mode operation. The indicator status is shown in table 3-3.

Table 3-3 Indicator status

LED

Status

Rectifier indicator

Green

Battery indicator

Green

Bypass indicator

Off

Inverter indicator

Green

Load indicator

Green

Status indicator

Green

3.2.2 Operating steps of

Battery cold Start

1.

Check if the batteries have been connected, close the external battery switch.