beautypg.com

8 rs232 port and snmp card port – OPTI-UPS MD120L User Manual

Page 75

background image

Chapter 1 Installation

18

J9

A

L

A

R

M

_

N

C

A

L

A

R

M

_

N

O

G

N

D

Fig 1-18 Integrated warning dry contact interface diagram

Table 1-8 Integrated warning dry contact interface description

Position

Name

Purpose

J9.1

ALARM_NC

Integrated warning relay (normally closed) will be open during warning

J9.2

ALARM_NO

Integrated warning relay (normally open) will be closed during warning

J9.3

GND

Centre of integrated warning relay

1.7.7 Mains Failure Warning Output Dry Contact Interface

J10 is the output dry contact interface for mains failure warning, when the mains fails, the system

will send a mains failure warning information, and provide an auxiliary dry contact signal via the isolation

of a relay. The interface diagram is shown in fig 1-19, and description is shown in table 1-9.

J10

U

T

I_

F

A

IL

_

N

C

U

T

I_

F

A

IL

_

N

O

G

N

D

Fig 1-19 Mains failure warning dry contact interface diagram

Table 1-9 Mains failure warning dry contact interface description

Position

Name

Purpose

J9.1

UTI_FAIL_NC

Mains failure warning relay(normally closed) will be open during

warning

J9.2

UTI_FAIL_NO

Mains failure warning relay (normally open) will be closed during

warning

J9.3

GND

Centre of mains failure warning relay

1.7.8 RS232 Port and SNMP Card Port

RS232 and RS485 Port: provide serial data which can be used for commissioning and maintenance

by authorized engineers or maintainers, or can be used for networking or integrated monitoring system in

the service room.

SNMP Card Port: used for field installation of the communication option card(SNMP card).

This manual is related to the following products: