Appendix A Guidebook to Ordering and Selection of MD System

MD series UPS module can be divided into equipment cabinet and power module. For the cabinet

lectotype please refer to the description in fig 6-1.

Fig 6-1 Cabinet Selection

For single power module type please refers to the description in fig 6-2:

Fig 6-2 Power Module Selection

Egg: the requirements of a plant room are given below:

The maximum power supply of the plant room is 120kVA; however, it is expected to be expanded to

200kVA in 3-5 years. Therefore, a 200kVA cabinet and 6 20kVA power module can be purchased to

constitute an uninterrupted 120kVA power system which can be expanded to 200kVA on-line. The order

symbol is:

1 set MD200/20

6 set MU20

Option list:

MD-SNMP card: remote network monitoring card

MD-1600 dust filter: dust screen for 1.6m cabinet

MD-2000 dust filter: dust screen for 2m cabinet

Represents the capacity of a single power module

10 represents 10kVA

15 represents 15kVA

20 represents 20kVA

represents a single power module

Represents UPS system capacity/power module

60/10 represents 60kVA/10kVA:

90/15 represents 90kVA/15kVA:

120/20 represents 120kVA/20kVA:

150/15 represents 150kVA/15kVA

200/20 represents 200kVA/20kVA

RM represents UPS cabinet