7.6 Electrical Characteristics (Inverter Output)
Table 7-6 Inverter Output (to important load)
Rated
capacity(kVA)
Unit
6~120KVA
Rated AC voltage
1
Vac
200/208(three-phase four-wire and sharing neutral with the
bypass)
Freqency
2
Hz
50/60
overload
%
105% load, long term operation
110% load, 1 hour
125% load, 10min
150% load, 1min
>150% load, 200ms
Fault current
%
340% short current limitation for 200ms
Non linear load
capability
3
%
100%
Neutral current
capability
%
170%
Steady state
voltage stability
%
±1(balanced load)
±2(100% imbalance load)
Transient voltage
response
4
%
±5
THD
%
<2(linear load) , <5(non linear load
3
)
Synchronization -
Window
Rated frequency ±2Hz(selectable: ±1~±5Hz)
Max change rate of
synch frequency
Hz/s
1: selectable: 0.1~5
Inverter voltage
range
%V(ac) ±5
Note:
1.
Factory setting is 208V. Commissioning engineers can set to 200V.
2.
Factory setting is 50Hz. Commissioning engineers can set to 60Hz.
3.
EN50091-3(1.4.58) crest ratio is 3: 1.
4.
IEC62040-3/EN50091-3 including 0%~100%~0% load transient, the recovery time is half
circle to within 5% of stable output voltage.