34 Chapter 3 Operating Instructions

34

The load power is supplied by bypass. In the meantime, the rectifier starts up, rectifier indicator goes

green 30s later, at this time, the inverter will start up automatically, and transfer to inverter mode 1 min

later automatically.

3.

Close external battery switch, the battery indicator goes off. Check if the battery voltage on LCD

display is normal.

3.4 Procedure for Completely Powering down a UPS

If you need to power down the UPS completely, follow the procedures in section 3.3.4 to transfer the

UPS from normal mode to maintenance bypass mode.

If you need to isolate the UPS from the AC power supply, you should open the external input switch.

3.5 EPO Procedure

The EPO button on UPS operator control and display panel is designed to switch off the UPS in

emergency conditions (e.g., fire, flood, etc.).To achieve this, just press the EPO button, and the system

will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and

bypass output), and the battery stops charging or discharging.

If the input utility is present, the UPS control circuit will remain active; however, the output will be

turned off. To completely isolate the UPS, you need to open the external mains input supply to the UPS

rack.

3.6 Language Selection

The LCD is available in two languages: Chinese, English and a kind of optional language. (Korean,

Russian, Turkish and Traditional Chinese)

The language can be selected through LCD prompt window.

3.7 Control Password

When the LCD display

s “input control password 1”, the initial password is 12345678.