beautypg.com

12 commissioning, 4 initial lighting, 5 check the gas inlet pressure and gas rate – Glow-worm Ultracom cx User Manual

Page 39

background image

39

Commissioning should only be carried out by a

competent

person approved at the time by the Health and Safety

Executive.

12.4 Initial Lighting

NOTE: The combustion for this appliance has been

checked, adjusted and preset at the factory for operation

on natural gas (G20) as defined on the appliance data

label.

No measurement of the combustion is necessary.

Having checked :

● the appliance has been installed in accordance with the

instructions.

● the integrity of the flue system and flue seals.

● the integrity of the appliance combustion circuit and

relevant seals.

● check that all external controls are calling for heat. If

the integral programmer is fitted check that it is correctly

programmed and if necessary overridden to provide heat.

● the gas service isolation valve ‘F’, diagram 12.2, is open.

LPG Conversion:

See section 12.9.

The lighting procedure of the boiler is fully automated.

Ensure that both the central heating water temperature and

the hot water temperature control knobs are turned OFF (0).
Ensure the mains electrical supply and turn the mains reset

knob to (I) on the controls fascia.
Turn the central heating water temperature control knob to

MINIMUM.
The digital display will show water temperature in central

heating demand.
The fan should start and after a few seconds the ignition will

commence
If the burner fails to light the fan will stop. Initially this may be

due to air in the gas supply line. The boiler will automatically

have five attempts at ignition.
If necessary press the reset switch and the boiler will restart.
After the boiler has lit, allow to warm at

MINIMUM

temperature setting to purge any air from the system.
NOTE: If the appliance is operated above MINIMUM on initial

lighting, there is a possibility that the overheat lockout and

“F5” will be displayed on controls fascia, this is due to air not

having been completely purged. See diagram 12.1 for reset

button.
Once the system has been purged of air turn the Hot water

temperature control knob to the desired position and open a

hot water tap. The diverter valve motor will move to hot water

supply and the display will read system pressure. Check that

hot water is available and then close the hot water tap.
Turn the Central heating water temperature control knob to

the desired temperature.
The appliance will then continue to fire in central heating until

the user controls are satisfied or there is another demand

made for hot water.

12.5 Check the Gas Inlet Pressure and Gas

Rate

Check the supply pressure at the gas service isolation valve

test point, see diagram 12.2.

12 Commissioning

13659

The nominal supply pressure should be 20mbar (8in wg)

when the appliance is operating at the maximum heat input.

This can be achieved by turning on several hot water taps.
NOTE:

There is a pressure drop over the gas service isolation

valve prior to the inlet pressure test point, this is normal and

the inlet pressure to the main gas valve can be up to 2mbar

less than the supply pressure to the boiler at the maximum

heat input. Additionally the safe nominal maximum heat input

of the appliance can be achieved at an inlet pressure down to

15mbar.
The gas valve is factory set for natural gas (G20) and should

need no adjustment.
Should any doubt exist about the gas rate, check it using the

gas meter test dial and stop watch, at least 10 minutes after

the burner has lit, see table below, for approximate rates.

Make sure that all other gas burning appliances and pilot

lights are off.
It should be noted that the appliance will modulate the heat

input according to demand. This may affect the gas rates

measured if the appliance reaches its operating temperature

during the measurement.
Turn taps off and disconnect the pressure gauge.

Operational Gas Inlet Pressure

With ALL other gas appliances operating, check the

operational supply pressure at the gas service isolation valve

test point, see diagram 12.2.

The nominal supply pressure for Natural Gas (G20) is 20mbar.

The nominal supply pressure for LPG (G31) is 37mbar.

Turn the taps and appliances off, then disconnect the pressure

gauge.

Additionally the safe nominal maximum heat input of the

appliance can be achieved at an inlet pressure down to

15mbar.
NOTE:

The

BURNER PRESSURE cannot be measured and

is not used to measure the gas rate.

Gas Rate

Make sure that ALL other gas burning appliances and pilot

lights are off.

Check the gas rate using the gas meter test dial and stop

watch, at least 10 minutes after the burner has lit, see table

below for approximate rates.

In communal or LPG installations where the gas rate cannot

be measured it is acceptable to measure the combustion rate

as described in the servicing section. Reset the boiler.