18.4.2 Automatic

air

vent

Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

Remove the retaining clip (19). Remove the automatic air vent

(18).

Fit the new automatic air vent and ‘O’ ring ensuring the vent

cap is left loose.

Refi ll, vent and pressurise the boiler.

18.4.3

Low water pressure sensor

Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

Disconnect the electrical lead (4).

Remove the retaining clip (6), remove the low water pressure

sensor (5).

Fit the new low water pressure sensor.

Refi ll vent and pressurise the boiler.

18.4.4 Safety

discharge

valve

Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

Remove the low water pressure sensor as described in the

previous section.

Undo the safety discharge valve union and remove the pipe.

Disconnect the Central Heating isolation valve.

Remove the securing clips and withdraw the safety discharge

valve plastic housing (29).

Remove the safety discharge valve.

Fit new ‘O’ ring. Refi ll, vent and pressurise the boiler.

18.4.5

Flow sensor and impeller

Remove the the electrical connection (12).

Unclip the fl ow sensor (13).

Unscrew the impeller housing (28) and remove the impeller.

18.4.6 Bypass

Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

Remove the bypass valve retaining nut (26) to remove the

bypass from its housing (25).

After replacing the bypass, refi ll, vent and pressurise the

boiler.

18.4.7

3 way valve motor and diverter valve

Drain the boiler heating circuit as described in the appropriate

chapter "Draining".

Disconnect the electrical plug (2).

Remove the retaining clip (3).

Remove the three way valve motor (1).

Remove the diverter valve retaining nut.

Remove the diverter valve.

Fit new three way valve motor and diverter valve assembly.

Refi ll, vent and pressurise the boiler.

18.4.8

Plate-to-plate heat exchanger

Drain the boiler heating and domestic hot water circuits as

described in the appropriate chapter "Draining".

Remove the two securing screws (23).

Remove the plate-to-plate heat exchanger (17).

When replacing the plate-to-plate heat exchanger, ensure that

the four rubber sealing washers are fi tted into the hydroblock.

NOTE: The plate-to-plate heat exchanger only fi ts one way.

Refi ll, vent and pressurise the boiler.

MAINTENANCE

- 42 -