INSTALLATION

i

IMPORTANT:

All the drawings dimensions are shown in mm.

6 Appliance

location

6.1 Location

6.1.1 Instructions

Before choosing a site for the appliance, carefully read the safety

warnings and installation manual.

Ensure that wall to which the appliance will be mounted on is

structurally safe in order to support the weight of the appliance.

Ensure that the space that the appliance is to be installed

within allows the appliance to be installed and the clearances

maintained. This will ensure that the connections to the water,

gas and fl ue can be accessed and inspected (see chapter

Clearances).

Explain these requirements to the appliance user.

Do not install the appliance above another appliance that

could damage it (for example, above a cooker that might emit

steam or grease) or in a room, which has a lot of dust in the

atmosphere which is corrosive.

The boiler must be fi tted inside the property and exposed pipe

work may need to be protected from frost by fi tting a frost

thermostat.

6.1.2 Regulations

Location

This boiler is not suitable for outdoor installation.

This boiler is suitable for installation in bathroom zones 2 and 3.

Timber Frame Buildings

If the boiler is to be installed in a timber frame building it should

be fi tted in accordance with the Institute of Gas Engineers

document IGE/UP/7/1998. If in doubt seek advice from local gas

undertaking or Glow-worm.

6.2 Clearances

To allow periodic maintenance, ensure the distances indicated

on the diagram.

Additional clearances may be benefi cial around the boiler for

installation and servicing.

For fl ue installations where external access is not practicable,

consideration should be given for the space required to insert the

fl ue from inside the property, which may necessitate clearance

larger than those specifi ed in diagram.

ØA

ØA

+ 5 min.

600*

min.

0

min.

0

min.

200

min.

150

min.

Key

*

A removable compartment door can be placed a minimum 5 mm in

front of appliance. A clearance of 600 mm is required from a fi xed

surface.

The boiler and fl ue are suitable for installation onto and through

combustible materials provided that:

- Minimum 5mm clearance is maintained around the

circumference of the fl ue (air intake).

- The combustible surface and fi xings are suitable for

supporting the load.

- The minimum clearances from the boiler case are maintained.

6.3 Ventilation

6.3.1 Room

Ventilation

The boiler is room sealed so a permanent air vent is not required.

6.3.2

Cupboard or Compartment Ventilation

Due to the high effi ciency and low casing temperature of this

boiler, cupboard or compartment ventilation is not necessary.

Existing ventilation should be investigated for its purpose

before removing.

INSTALLATION