15 Gas conversion adjustments

In order to adjust the appliance to a diff erent gas that it is set to

in production.

This conversion should only be carried out by a competent person

approved at the time by the Health and Safety Executive.

During the conversion to Propane, use of a suitable fl ue gas

analyser is necessary.

The person carrying out a combustion measurement should have

been assessed as competent in the use of a fl ue gas analyser

and the interpretation of the results. The fl ue gas analyser used

should be one meeting the requirements of BS7927 or BS-

EN50379-3 and be calibrated in accordance with the analyser

manufacturers’ requirements. Competence can be demonstrated

by satisfactory completion of the CPA1 ACS assessment, which

covers the use of electronic portable combustion gas analysers in

accordance with BS 7967, parts 1 to 4.

15.1 Settings

i

IMPORTANT:

Steps "Switching on" to "Re-pressurising System" will

need to be completed before the appliance can be

converted (See chapter "Commissioning").

Tools required to make the conversion are a 4mm Allen key and

an electricians screwdriver.

Having checked :

- the appliance and system have been installed in

accordance with the instructions.

- the integrity of the fl ue system and fl ue seals....

- the integrity of the appliance combustion circuit and relevant

seals....

- that all internal/external controls are calling for heat.

- the gas service isolation valve is opened.

1

2

3

2B

2A

Key

1 Throttle

2 Combustion analyser sample point

2A Flue elbow

2B Vertical

fl ue adaptor

3 Cap

Remove the front panel fi rst.

Remove the cap (3) and connect a CO2 analyser to eff ect the

measurement (2).

15.1.1 Adjusting

the gas valve

Press the on/off button to turn the appliance off .

Turn the screw in the direction and the number of times

indicated in the following table.

Gas adjustment

Model

G20 > G31

G31 > G20

30

3 turns

35

2.5 turns

30

3 turns

35

2.5 turns

15.1.2

Adjusting the maximum power setting

Activate the test mode "P.01" and set the value to HI in order to

force the burner at P. max. See chapter "Specifi c adjustment >

Appliance technical settings and parameter list > Test modes".

Wait approximately 5 minutes to read a stabilized CO

2

value.

MAINTENANCE