Maintenance, 15 gas conversion adjustments – Glow-worm Ultimate c User Manual
Page 34
0020167175_01 - 02/13 - Glow-worm
15 Gas conversion adjustments
In order to adjust the appliance to a diff erent gas that it is set to
in production.
This conversion should only be carried out by a competent person
approved at the time by the Health and Safety Executive.
•
During the conversion to Propane, use of a suitable fl ue gas
analyser is necessary.
The person carrying out a combustion measurement should have
been assessed as competent in the use of a fl ue gas analyser
and the interpretation of the results. The fl ue gas analyser used
should be one meeting the requirements of BS7927 or BS-
EN50379-3 and be calibrated in accordance with the analyser
manufacturers’ requirements. Competence can be demonstrated
by satisfactory completion of the CPA1 ACS assessment, which
covers the use of electronic portable combustion gas analysers in
accordance with BS 7967, parts 1 to 4.
15.1 Settings
i
IMPORTANT:
Steps "Switching on" to "Re-pressurising System" will
need to be completed before the appliance can be
converted (See chapter "Commissioning").
Tools required to make the conversion are a 4mm Allen key and
an electricians screwdriver.
Having checked :
- the appliance and system have been installed in
accordance with the instructions.
- the integrity of the fl ue system and fl ue seals....
- the integrity of the appliance combustion circuit and relevant
seals....
- that all internal/external controls are calling for heat.
- the gas service isolation valve is opened.
1
2
3
2B
2A
Key
1 Throttle
2 Combustion analyser sample point
2A Flue elbow
2B Vertical
fl ue adaptor
3 Cap
•
Remove the front panel fi rst.
•
Remove the cap (3) and connect a CO2 analyser to eff ect the
measurement (2).
15.1.1 Adjusting
the gas valve
•
Press the on/off button to turn the appliance off .
•
Turn the screw in the direction and the number of times
indicated in the following table.
Gas adjustment
Model
G20 > G31
G31 > G20
30
3 turns
35
2.5 turns
30
3 turns
35
2.5 turns
15.1.2
Adjusting the maximum power setting
•
Activate the test mode "P.01" and set the value to HI in order to
force the burner at P. max. See chapter "Specifi c adjustment >
Appliance technical settings and parameter list > Test modes".
•
Wait approximately 5 minutes to read a stabilized CO
2
value.
MAINTENANCE
- 32 -