beautypg.com

10 electrical connections – Glow-worm Energy Saver 80 - 100 and Gave Valve User Manual

Page 19

background image

19

221564F

10.2 Heating System Controls

WARNING: Mains electricity must not be connected to the

black auxiliary control plug.
All heating system controls must be low voltage or potential

free.
It is recommended that the boiler is controlled by a programmer
and room thermostat. A suitable room thermostat is supplied in
the wall mounting pack.

Thermostatic radiator valves may be installed in addition to the
room thermostat.

Note: For further information, see The Building Regulations
1991 - Conservation of fuel and power, 1995 edition - Appendix
G, table 4b.

All system controls are wired into the black electrical connector
plug situated on the right hand side of the wall mounting jig.

If electrical controls are being used the links between terminals
should be removed as necessary as shown in diagram 10.3.

If electrical controls are not being used, DO NOT REMOVE the
red and blue links between terminals 1 and 2, and 2 and 3 in the
black electrical connector plug.

10.3 Clock/Timer

An integral clock/timer kit can be supplied as an optional extra.
Refer to the literature supplied with it, regarding fitting.

10.4 Frost Thermostat

This boiler has its own frost protection device to protect the
boiler. Additional frost protection may be required for exposed
pipework. If required, connect a single pole frost thermostat to
the appropriate terminals of the black electrical connector plug
as shown in diagram 10.3.

10.5 Outside Sensor

An outside sensor can be supplied as an optional extra, see
section 11.11. If required, connect to the red and black wires
which are pre-wired to terminals 4 and 5 of the control module.

10.6 Cable and Connector Securing

After completing all the connections to the wall mounting jig
electrical connectors, secure the cables with the covers, using
the screws previously removed.

Connect the boiler connector, and replace the cover plate over
the white mains connector, see diagram 10.4.

10.7 Electrical Connections - Testing

Carry out preliminary electrical system checks as below:

1. Test insulation resistance to earth of mains cables.

2. Test the earth continuity and short circuit of cables.

3. Test the polarity of the mains.

Diagram 10.2

6531

MAINS ELECTRICAL
SUPPLY SOCKET

EARTH

(L) LIVE

(N) NEUTRAL

Diagram 10.1

MAINS ELECTRICAL
COVER PLATE

SECURING
SCREW

6571

BRACKET

Diagram 10.3

6553

FROST THERMOSTAT

ROOM
THERMOSTAT

CLOCK
TIMER

RED LINK

BLUE LINK

Diagram 10.4

APPLIANCE
PLUG

MAINS IN
SUPPLY PLUG

COVER
PLATE

SCREW

WARNING : Mains electricty must not be connected to

the black auxiliary control plug.

6596

10 Electrical Connections