3.4 Terminal Guard

A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.

If a terminal guard is required, it must be positioned to provide
minimum of 50mm clearance from any part of the terminal and
be central over the terminal.

The guard should be similar to that shown in diagram 3.5.

A suitable guard can be obtained from.

Tower Flue Components

Morley Rd.

Tonbridge

Kent

TN9 1RA.

Their Reference CGD K3 BL.

3.5 Timber Frame Buildings

If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Hepworth Heating Ltd.

3.6 Room Ventilation

The boiler is room sealed, so when it is installed in a room or
space, a permanent air vent is not required.

3.7 Cupboard or Compartment Ventilation

Due to the high efficiency and hence low casing temperature of
this boiler, cupboard or compartment ventilation is not necessary.

3 Flue Location and Ventilation

A

A

F

G

E

A

G

G

G

B,C

B,C

F

F

K

K

K

C

G

L

L

UNDER CAR PORT etc.

H,I

J

D

F

K

2816

Diagram 3.4

MINIMUM SITING DIMENSIONS FOR

FANNED FLUE TERMINALS

POSITION

MM

A DIRECTLY BELOW AN OPENABLE

WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING

300

B BELOW GUTTER, DRAIN/SOIL PIPE

75

C BELOW EAVES

200

D BELOW A BALCONY OR CAR PORT

200

E FROM VERTICAL DRAIN PIPES AND

SOIL PIPES

75

F FROM INTERNAL CORNERS

300

*

G ABOVE ADJACENT GROUND OR

BALCONY LEVEL

300

H FROM SURFACE FACING THE

TERMINAL

600

*

I

FACING TERMINALS

1200

J FROM OPENING (DOOR/WINDOW)

IN CAR PORT INTO DWELLING

1200

K VERTICAL FROM A TERMINAL

1500

L HORIZONTALLY FROM A TERMINAL 300
M FROM EXTERNAL CORNERS

300

M

Diagram 3.5

TERMINAL GUARD

*

It may be necessary to increase this dimension to prevent

staining of adjacent walls depending on weather conditions.