4.1 General

The boiler is for use in sealed water systems only.

The safety valve is an integral part of the boiler and it cannot be
adjusted.

A pressure gauge is incorporated into the boiler to indicate the
system pressure.

The circulation pump is integral with the boiler, see diagram 4.1.

4.2 Expansion Vessel

The boiler has an integral expansion vessel with a capacity of
7 litres (1.54 gallons), with a charge pressure of 0.5bar.

The maximum heating system water content using the fitted
expansion vessel is 130 litres at an average temperature of
75

O

C, and charge pressure of 1.0bar.

4.3 Flow Rate

The minimum flow rate through the boiler is 400 litres/hr for

ES80 and 470 litres/hr for ES100. This is equal to 20

O

C

differential at maximum heat input.

The system can be fitted with a lockable balancing valve if
necessary in the main flow or return pipes shown as valve "A"

in diagram 4.2.

Diagram 4.1

6558

7

METRES WG

UPS 15-60 PUMP

AVAILABLE PUMP HEAD

BOILER PRESSURE LOSS CUR

VE

= SETTING 1

= SETTING 2
= SETTING 3

0

0

0.25 0.5 0.75

1.0 1.25 1.5

1.75 2.0 2.25 2.5

1

2

3

4

5

6

HEATING SYSTEM FLOW RATE X 1000 l/hr

4.4 Bypass

The boiler is fitted with a manual bypass, see diagram 4.3. This
valve may be adjusted by the installer if necessary to ensure at

least 400 litres/hr for ES80 and 470 litres/hr for ES100 flow
through the boiler. The boiler is supplied with the bypass open
by approximately half a turn and is closed by turning the white
screw clockwise. However for systems completely fitted with
thermostatic radiator valves or systems of high pressure loss an
additional bypass valve must be fitted to the heating circuit to

ensure that under no circumstances does the flow rate drop
below this level.

An additional bypass valve “B” is shown in diagram 4.2.

4.5 Filling Sealed Systems

Provision for filling the system at a low level must be made. Two
methods of filling are shown in diagram 4.4. There must be no
permanent connection to the mains water supply, even through
a non-return valve.

4 Heating System