beautypg.com

8 fault finding – Glow-worm Clearly Solar System Hydraulics User Manual

Page 24

background image

24

8 Fault Finding

Malfunction

Cause

Remedy

Only cold or lukewarm water comes out

of the taps.

1. Cold and hot water connections on the

cylinder have been mixed up.

Turn off the cold water supply, then

let water flow out via the hot water

connection. Only a few litres of water

flow out if the connection is laid correctly.

The inlet of the hot water draw-off pipe

then rests in the air space; no further

emptying is possible. If the entire solar

cylinder runs empty via the hot water

connection, the connections have been

laid incorrectly. Change the connections!

2. Hot water thermostat mixer set too low. Increase the setting.
3. Solar heating insufficient; boiler does

not reheat.

External control device faulty.

Air in the reheating heat exchanger

Cylinder temperature sensor defective.

Check whether the boiler is working.

Check whether the external control

device is working.

Check whether the two port valve is in the

hot water position.

Replace the two port valve.

Bleed the reheating heat exchanger.

Check the thermal cut out and reset it.

Replace the cylinder thermostat.

Water flows out of the expansion relief

valve (only when heating up).

Dirt on the valve seat of the expansion

relief valve.

Check the expansion relief valve and

reset it manually.

Pressure limiting valve defective.

Switch off the boiler and immersion

heater and check whether the pressure

behind the pressure limiting valve is lower

than 3.0 bar if water flows out only when

heating up. If so, replace the pressure

limiting valve.

Expansion vessel defective.

Check the pressure in the expansion

vessel. If the pressure is insufficient,

re-establish the pressure and check

whether the equalisation tank maintains

the pressure.

Expansion relief valve defective.

If the pressure is normal, replace the

expansion relief valve.

Water comes out of the temperature and

pressure relief valve (only when heating

up).

Dirt on the valve seat of the temperature

and pressure relief valve.

Check the seat of the temperature

and pressure relief valve and reset it

manually.

Temperature control of the boiler

defective.

Check the temperature control of the

boiler if water only comes out when

reheating with the boiler. Check whether

the two port valve switches to the heating

position after reaching the cylinder

temperature.

Cylinder temperature sensor defective.

Check the cylinder temperature sensor

and the corresponding thermal cut outs

and replace the temperature sensor and

reset the thermal cut outs if necessary.

Two port valve defective.

Check whether the two port valve is

working and replace it if necessary.

Temperature and pressure relief valve

defective.

Replace the temperature and pressure

relief valve if water only comes out when

heating up with the immersion heater.

Immersion heater defective.

Check the temperature sensor of the

immersion heater and the corresponding

thermal cut out and replace the

immersion heater if necessary.

Table 8.1 Fault Finding (continued)