Maintenance – Glow-worm Clearly Hybrid - Universal Module System User Manual
Page 31
![background image](/manuals/736737/31/background.png)
0020096317_01 - 02/11 - Glow-worm
- 29 -
Fault
codes Description
Cause
Solution
030
Failure in communication with the zone
1 wireless room thermostat.
The room thermostat is too far from
the control unit.
There is a problem with the batteries
in room thermostat.
Check the RF signal quality via the Climapro2 RF installer
menu.
Check the location of the thermostat.
Check that the thermostat’s batteries are installed in their
compartment.
Make sure the battery polarity is not reversed.
Make sure the batteries are not dead.
If so, replace them with new batteries
031
Failure in communication with the zone
2 wireless room thermostat.
032
Failure in communication with the zone
3 wireless room thermostat.
033
Failure in communication with the zone
4 wireless room thermostat.
034
Failure in communication with the zone
5 wireless room thermostat.
035
Failure in communication with the zone
6 wireless room thermostat.
036
Failure in communication with the
wireless outdoor sensor
The wireless outdoor sensor is too far
from the control unit.
Check the location of the outdoor sensor. Check that the
sensor’s power supply is correctly provided by a photovoltaic
cell.
MAINTENANCE
EN