- 28 -

MAINTENANCE

11 Trouble-shooting

11.1 Fault

diagnosis

The following checks should be performed before proceeding

onto specifi c diagnostics:

- Make sure that the electricity supply has not been interrupted

and that the appliance is connected correctly.

- Ensure that the isolating valves are open.

- Check that all external controls are connected correctly.

11.2 System fault codes

i

The faults described in this chapter should be carried

out by a qualifi ed engineer and if needed by the After

Sales Service.

Refer to the instructions for each element making up the

system for their fault codes.

Fault

codes Description

Cause

Solution

001

Failure in Ebus communication between

with the boiler

The boiler is not connected to the

control unit.

The cable polarity is reversed.

The boiler is off .

Check that the boiler is connected to the control unit.

Check the connection’s + / - polarity.

Ensure that there is no interruption to the electricity network

and that the boiler is properly connected and turned on.

002

Failure in Ebus communication between

with the heat pump

The heat pump is not connected to the

control unit.

The heat pump is off .

Make sure the heat pump is connected to the control unit.

Ensure that there is no interruption to the electricity network

and that the heat pump is properly connected and turned on.

003

Failure in Ebus communication between

with the hydraulic module

The hydraulic module is not connected

to the control unit.

The hydraulic module is off .

Make sure that the hydraulic module is connected to the

control unit.

Ensure that there is no interruption to the electricity network

and that the hydraulic module is properly connected and

turned on.

010

Heating circuit fl ow temperature sensor

failure (open circuit)

The sensor is defective or not

properly connected to the control unit

management or hydraulic module.

Check the sensor’s connections.

Verify that the position and the operation of the sensor are

correct.

Check the sensor’s resistance.

011

Heating circuit fl ow temperature sensor

failure (short circuit)

The sensor is shorted.

012

Heating circuit fl ow temperature sensor

failure low temperature (open circuit)

The sensor is defective or not properly

connected to the control unit.

Check the sensor’s connections.

Verify that the position and the operation of the sensor are

correct.

Check the sensor’s resistance.

013

Heating circuit fl ow temperature sensor

failure low temperature (short circuit)

The sensor is shorted.

014

Domestic water tank temperature

sensor failure (open circuit)

The sensor is defective or not properly

connected to the control unit.

Check the sensor’s connections.

Verify that the position and the operation of the sensor are

correct.

Check the sensor’s resistance.

015

Domestic water tank temperature

sensor failure (short circuit)

The sensor is shorted.

021

Pressure too low <0.5 bar

There is a leak in the heating circuit.

The venting was not carried out

correctly.

Check that there are no leaks.

Drain the heating circuit. Remove air.

Fill the installation.