18 Fault Finding

FAULT: THE FAN DOES NOT START.

Check continuity of fan harness.

NO

YES

Is there 230V ac

at fan during demand?

Faulty fan, replace.

YES

Faulty C, replace.

FAULT: THE WATER AT THE TAPS IS LUKE-WARM.

NO

YES

Check that the flow restrictor on the cold
water inlet is fitted.
Check the rate of flow.
Check burner pressure is correct.

Check the 3-way valve is not passing
into the radiators. (The radiators should
stay cold in Summer setting)

Is the temperature higher if you reduce

the flow through the taps?

9966p

9968p

• CHECK CONTINUITY OF IGNITION (ELECTRODES AND LEADS)
• CHECK POWER SUPPLY FROM PCB TO IGNITION UNIT

Air flow switch take-off.

CONNECTIONS TO THE AIR PRESSURE SWITCH

Pr

3

2

1

P2

P1

L

H

Electrical contacts.

FAULT: THE FAN RUNS BUT THERE ARE NO SPARKS.