7.5 Alarm
Visual alarms provided: for each channel
•
fault signal lamp:
channel in service: green color
channel off or malfunction of microprocessor: off
disturbance on line: steady yellow color
calibration/adjustment mode: blinking yellow color
•
alarm 1 signal lamp: red color when in alarm
•
alarm 2 signal lamp: red color when in alarm
•
alarm 3 signal lamp: red color when in alarm
Alarms 1 and 2
•
activation after 5 seconds
•
by increasing or decreasing value
•
manual or automatic clearance
Alarm 3
•
activation after elapsed delay time or on basis of average value
•
automatic clearance
•
by increasing or decreasing value
Disturbance
•
complete check of short circuit or cut out of at least one wire (with just one detector)
•
display per channel with yellow signal lamp
Buzzer
Triggered if:
microprocessor malfunction
anomaly of connecting cable or sensor/transmitter
alarm threshold level exceeded
maintenance time longer than 30 minutes