0 troubleshooting – ENMET MX-42A User Manual
Page 18
ENMET Corporation
MX42A C
ONTROL
14
6.0 Troubleshooting
6.0 Troubleshooting
6.0 Troubleshooting
6.0 Troubleshooting
Fault message
Possible Cause
Corrective action
Display off or no LED lighted
fuse blown
power switch set to
OFF
check power supply voltages and change the
fuses if necessary
set the power switch to
ON
STOP
displayed
channel out of service
put the channel microswitch 8 to
ON
INIT
displayed
bad detector electrical connections
defective detector
the type of detector does not
correspond to the configuration of
the channel
channel very badly adjusted
check the connections
change the detector
change the type of detector
Caution: The channel could have been damaged
adjust the channel
Fault signal lamp lighted and
DEF
displayed
Fault signal lamp blinking
channel in maintenance mode for
more than 30 minutes
channel in maintenance position
reset the channel microswitch 7 to
NORMAL
reset the channel microswitch 7 to
NORMAL
External alarm controlled in
opposite direction, in relation
to the tripping of the alarm
bad choice of relay contact
move the jumper to use the correct contact