beautypg.com

4 outputs, Figure 8: relay jumper and 4-20ma pot location – ENMET MX-42A User Manual

Page 16

background image

ENMET Corporation

MX42A C

ONTROL

12

4.4 Outputs

4.4.1 Relays

With the position of jumpers

S3

through

S12

, the contacts of the relays for each channel can be selected. The

contacts can be either open or closed during the alarm condition. see F

IGURE

8. The factory set position is normally

closed.

This selection is made by moving the corresponding jumper. The standard factory setting, relays (except for the fault
relay) are energized in the non-alarm condition.

4.4.2 4-20 mA Current Output

A 4-20 mA output is available on the terminal block for each channel. It serves to connect the

MX 42A C

ONTROL

to a

chart recorder or to any other data acquisition system (maximum load resistance is 600 ohms).

N

OTE

:

The 4-20 mA output is preset in the factory: 4 mA corresponds to a display of 0 and 20 mA corresponds to a

full-scale value.

Potentiometers P5, P6, P7 and P8 (for channels 1, 2, 3 and 4 respectively) adjust the 4 mA.

Potentiometers P21, P22, P23 and P24 (for channels 1, 2, 3 and 4 respectively) adjust the 20 mA

Figure 8: Relay Jumper and 4-20mA POT Location

Jumpers

S3 to S12

P5

P21

P6

P22

P7

P23

P8

P24

Jumper position
for NC contact

Jumper position
for NO contact