beautypg.com

0 installation – ENMET ISA-44-2OD User Manual

Page 11

background image

ISA-44-2-OD

ENMET Corporation

7

3.0 Installation

3.0 Installation

The ISA-44-2-OD is completely oiltight and watertight. Use the correct watertight fitting for the cord or conduit
when supplying power to the unit.

3.1 Power Hook-Up and Mounting of Control Unit ISA-44-2-OD

1. Choose a suitable location for mounting the electronics control unit.

2. The

OPERATE

switch should be in the

HORN OFF

position.

3. Open the control unit. Remove the terminal strip cover from TB-6 (see Figure 2 and 4). Simply pull the cover

off the holding prongs.

4. Apply 115 V

AC

, 220 V

AC

* and/or 12 V

DC

power to the proper terminals. Refer to Figure 4.

NOTE: 220 V

AC

power requires a change in the transformer hook-up by a competent electrician or electronics

technician; but this change is best done at ENMET. Both

AC

and

DC

power can be applied at the same time.

Current will flow from the

AC

source;

DC

current (as emergency back-up power) will flow ONLY when the

AC

power is interrupted.

5. Run the relay contacts through the same watertight fitting as the power cord leads or out a second fitting. Be sure

to use watertight fittings that meet NEMA-4X standards. See Figure 8 for an example of relay wiring. When the
power supply is interrupted, the relays switch to the same position as for the true gas alarm condition and the
power lights (green) are off. Do Not Connect the Unit to Other Voltage Supply Lines.

6. Replace the terminal strip cover on TB-6. Make sure the cover fits snugly into the prongs.

Figure 5: Mounting Dimensions ISA-44-2-OD

TB2

TB6

TB1

TB3

TB4

TB5