Delta Electronics Network Device IFD9506 User Manual

Delta Electronics Hardware

background image

Warning

This instruction sheet only provides introductory information on electrical specification, installation and wiring.
Switch off the power before wiring. DO NOT touch any terminal when the power is switched on.
IFD9506 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,

electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key

or specific tools are required to open the enclosure) in case danger and damage on the device may occur.

Introduction

Features

1. Auto-detects 10/100 Mbps transmission speed; MDI/MDI-X auto-detection.

2. The monitor table temporarily stores the monitored data for the user to fast save or acquire the data.

3. Supports Modbus TCP protocol (supports Master and Slave mode)

4. Able to send out emails after being triggered.

5. The station address, RS-485 communication format and baud rate can be set up externally.

6. The communication parameters can be set up through Web.

Product Profile & Outline

9

1

Communication ports: RS-485,
Ethernet, RS-232

2

Power indicator

3

Address switch

4

Data format/baud rate switch

5

Digit display

6

RS-485 indicator, Reset button,
Ethernet indicator

7

Module name

8

RS-485 connector, digital input points,
power input point, earth point

9

DIN rail connector

Specifications

Ethernet Interface

Interface

RJ-45 with Auto MDI/MDIX

Transmission method

Ethernet Type II

Transmission cable

Category 5e, 100m (Max)

Transmission speed

10/100 Mbps Auto-Detection

Network protocol

ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta
Configuration

ENGLISH

RS-485 Connector

Interface

RJ-11

Transmission method

RS-485

Transmission speed

110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200

Communication format

Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU

Communication
protocol

Modbus, User Define

RS-232 Connector

Interface

Mini Dim

Transmission method

RS-232

Transmission speed

110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200

Communication format

Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU

Communication
protocol

Modbus, Delta Configuration, User Define

Transmission cable

DVPACAB215 / DVPACAB230 / DVPACAB2A30

Terminal Block

Interface

Feed-through terminal 10PIN

Transmission method

RS-485

Transmission distance

1,200m

Transmission speed

110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200

Communication format

Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU

Communication
protocol

Modbus, User Define

Electrical Specifications

Power voltage

24V DC (-15% ~ 20%) supplied by feed-through terminal

Power consumption

3W

Insulation voltage

500V

Weight

140g

Environment

Noise immunity

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz,
10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~
80MHz, 3V/m
Surge Test (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM

Operation/storage

Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)

Vibration/shock
immunity

International standards: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC
68-2-27(TEST Ea)

Certificates

Installation

Dimension

Unit: mm

Address Switch

Switch setting

Content

01 … F7

Valid Modbus communication address

Data Format Switch

Switch setting

Format

Switch setting

Format

0

7-N-1

8

7-N-2

1

8-N-1

9

8-N-2

2

7-O-1

A

7-O-2

3

8-O-1

B

8-O-2

6

7-E-1

E

7-E-2

7

8-E-1

F

8-E-2

Baud Rate Switch

Switch setting

Baud rate (bps) Switch setting

Baud rate (bps)

1

110

7

4,800

2

150

8

9,600

3

300

9

19,200

4

600

A

38,400

5

1,200

B

57,600

6

2,400

C

115,200

RJ-11 PIN Definition

PIN

Signal

Definition

PIN

Signal

Definition

1

--

N/C

4

D-

Negative pole for data

2

--

N/C

5

GND

Ground

3

D+

Positive pole for data

6

--

N/C

RJ-45 PIN Definition

PIN

Signal

Definition

PIN

Signal

Definition

1

Tx+

Positive pole for data

transmission

5

--

N/C

2

Tx-

Negative pole for data

transmission

6

Rx-

Negative pole for data

receiving

3

Rx+

Positive pole for data

receiving

7

--

N/C

4

--

N/C

8

--

N/C

RS-232 PIN Definition

PIN

Signal

Definition

PIN

Signal

Definition

1

--

N/C

5

Tx

Transmission data

2

--

N/C

6

--

N/C

3

--

N/C

7

--

N/C

4

Rx

Reception data

8

GND

Ground

Feed-through Terminal PIN Definition

PIN

Signal

Definition

1

SG

Ground of signal

2

D-

Data-

3

D+

Data+

4

X2

Digital input 2

5

X1

Digital input 1

6

X0

Digital input 0

7

S/S

Ground of digital input

8

24V

+24V

9

0V

0V

10

--

Earth ground

LED Indicators & Trouble-Shooting

There are 3 LED indicators and a digital display on IFD9506. POWER indicator displays the status of the

working power. RS-485 and LINK/ACT indicators display the connection status of the communication. The

digital display shows the address of and errors in IFD9506 and the error messages from the slave.

POWER LED

LED status

Indication

How to correct

OFF

Working power is abnormal

Check if the working power of IFD9506 is normal.

Green light ON Working power is normal

--

RS-485 LED

LED status

Indication

How to correct

OFF

No communication or RS-485
connection is abnormal.

1. If the LED is off during the communication, check if the RS-485 in

IFD9506 is normally connected.

2. Check at least 1 node on the network is communicating normally.

Constantly ON

Abnormal RS-485 connection

Switch D+ and D-

Green light
flashes

RS-485 connection is normal.

--

LINK/ACT LED

LED status

Indication

How to correct

OFF

No power, or no network
connection

1. Check the power of IFD9506 and make sure the network

connection is normal.

2. Re-power IFD9506. If the error still exists, send your IFD9506

back to the factory for repair.

Green light ON

The connection is normal, but no
data transmission.

--

Green light
flashes

The data transmission is normal. --

Codes in Digital Display

Code

Indication

How to correct

01 ~ F7

The node address of IFD9506 when
in normal operation

--

F0

Returning to default setting

--

F1

IFD9506 is booting

--

F2

Working power in low voltage

Check if the working power is normal.

F3

Internal memory error

1. Re-power IFD9506. If the error still exists, try step 2.
2. Reset IFD9506. If the error still exists, send it back to the factory

for repair.

F4

Internal error caused by
manufacturing in the factory

1. Re-power IFD9506. If the error still exists, try step 2.
2. Reset IFD9506. If the error still exists, send it back to the factory

for repair.

F5

Network connection error

Check if IFD9506 is normally connected to the network.

F6

Full number of devices connected in
the network

Check if the number is too much.

F7

UART setting error.

Check if the RS-485, RS-232 communication format is correct.

E1

Alarm 1 triggered

Check Alarm Input Point 1.

E2

Alarm 2 triggered

Check Alarm Input Point 2.

E3

Alarm 3 triggered

Check Alarm Input Point 3.

01

Incorrect

MODBUS

function

Check if the Modbus instruction is correct.

02

Incorrect address

Check if the Modbus instruction is correct.

03

Incorrect data

Check if the Modbus instruction is correct.

04

CRC error

1. Check if IFD9506 and RS-485 is connected normally.
2. Check if the series transmission speed is consistent with that of

other nodes on the network.

0B

No response from the station

1. Check if IFD9506 and RS-485 is connected normally.
2. Check if the series transmission speed is consistent with that of

other nodes on the network.

注意事項

此安裝手冊只提供電氣規格、一般規格、安裝及配線等。

配線時請務必關閉電源,請勿在上電時觸摸任何端子。

本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊∕
衝擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開),防止非維護人員操作
或意外衝擊本體,造成危險及損壞。

產品簡介

功能特色

1.

自動偵測 10/100 Mbps 傳輸速率,MDI/MDI-X 自動偵測。

2.

提供 Monitor table 可暫存監控的資料,讓使用者快速存取。

3.

支援 Modbus TCP 協定 (支援 Master 和 Slave 模式)。

4.

經觸發後發送電子郵件。

5.

可由外部設定站號、RS-485 通訊格式、鮑率。

6.

可由 Web 設定通訊參數。

產品外觀

1

通訊口 RS-485, Ethernet,
RS-232

2

電源指示燈

3

站號設定開關

4

通訊格式、通訊速率設定開關

5

數位顯示器

6

RS-485

指示燈、Reset 按鍵、

Ethernet

指示燈

7

模組名稱

8

端子台 RS-485 連接器、數位輸入

點、電源輸入、大地

9

9

DIN

軌連接器

功能規格

Ethernet 連接器

接頭

RJ-45 with Auto MDI/MDIX

傳輸方式

Ethernet Type II

傳輸電纜

Category 5e, 100

公尺 (Max)

傳輸速率

10/100 Mbps Auto-Detection

網路協定

ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta Configuration

繁體中文

RS-485 連接器

接頭

RJ-11

傳輸方式

RS-485

傳輸速率

110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200

通訊格式

Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU

通訊協定

Modbus, User Define

RS-232

連接器

接頭

Mini Dim

傳輸方式

RS-232

傳輸速率

110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200

通訊格式

Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU

通訊協定

Modbus, Delta Configuration, User Define

傳輸電纜

DVPACAB215 / DVPACAB230 / DVPACAB2A30

端子台連接器

接頭

歐式端子台 10PIN

傳輸方式

RS-485

傳輸距離

1,200m

傳輸速率

110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200

通訊格式

Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU

通訊協定

Modbus, User Define

電氣規格

電源電壓

24V DC (-15% ~ 20%)

由歐式端子台輸入

消耗電力

3W

絕緣電壓

500V

重量

140g

環境規格

雜訊免疫力

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~ 80MHz,

3V/m

Surge Test (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM

操作∕儲存環境

操作:0ºC ~ 55ºC(溫度)、50 ~ 95%(濕度)、污染等級 2
儲存:-25ºC ~ 70ºC(溫度)、5 ~ 95%(濕度)

耐震動∕/衝擊

國際標準規範 IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27(TEST
Ea)

標準