FIGURE 54 — FAN MOTOR TROUBLESHOOTING CHART

TYPICAL 208/230 VOLT MOTORS

NOTE: Resistance values are approximate.

TYPICAL 265 VOLT MOTORS

NOTE: Resistance values are approximate.

FIGURE 55 — TYPICAL 52C,P FAN MOTORS

POSSIBLE CAUSE

SYMPTOM

MOTOR HUMS

BUT DOES

NOT START

MAKES NO NOISE

AND DOES NOT

START

STARTS BUT

STOPS AFTER

SHORT TIME

STARTS

BUT RUNS

SLOW

RUNS ON

ONE SPEED,

NOT ON OTHERS

DEFECTIVE BEARING

X

X

X

CAPACITOR DEFECTIVE

X

X

SWITCH DEFECTIVE

X

X

LOW LINE VOLTAGE

X

X

X

SHORTED MOTOR WINDING

X

X

X

NO POWER TO UNIT

X

INTERNAL THERMOSTAT OPEN

X

MISWIRED

X

X

X

X

FAN STUCK

X

BROKEN MOTOR WIRE

X

X

X

X

MOTOR WINDING GROUNDED

X

X

OPEN MOTOR WINDING

X

X

X

X

UNIT 52C,P (BTUH)

7,000/9,000

12,000/15,000

CARRIER MOTOR PART NUMBER

HC37GE237

HC37GE238

MANUFACTURER’S

PART NUMBER

5KCP29ECA299A

5KCP29ECA301

MOTOR VOLTAGE

208/230

208/230

MOTOR HORSEPOWER

.075

.125

MOTOR SPEEDS

2

2

RESISTANCE (OHMS)

BLACK TO WHITE WIRE

101.4

90

RESISTANCE (OHMS)

BLACK TO BROWN WIRE

45.8

71

RESISTANCE (OHMS)
BLACK TO RED WIRE

38.8

32.9

UNIT 52C,P (BTUH)

7,000/9,000

12,000/15,000

CARRIER MOTOR PART NUMBER

HC29GE236

HC33GE239

MANUFACTURER’S

PART NUMBER

5KCP29FCA315

5KCP29FCA316

MOTOR VOLTAGE

265

265

MOTOR HORSEPOWER

.075

.125

MOTOR SPEEDS

2

2

RESISTANCE (OHMS)

BLACK TO WHITE WIRE

144.0

83.7

RESISTANCE (OHMS)

BLACK TO BROWN WIRE

29.3

39.1

RESISTANCE (OHMS)
BLACK TO RED WIRE

82.1

45.2