Generac IM-72LP Industrial Mobile Generator
DANGER: BAHERY ELECTROLYTE FLUID
IS AN EXTREMELY CAUSTIC SULFURIC ACID
SOLUTION THAT CAN CAUSE SEVERE BURNS.
DO NOT PERMIT FLUID TO CONTACT EYES, SKIN,
CLOTHING, PAINTED SURFACES, ETC. WEAR
PROTECTIVE GOGGLES, PROTECTIVE CLOTHING
AND GLOVES WHEN HANDLING A BAHERY. IF
YOU SPILL THE FLUID, FLUSH THE AFFECTED
AREA IMMEDIATELY WITH CLEAR WATER.
DANGER: DO NOT USE ANY JUMPER CABLES
OR BOOSTER BAHERY TO CRANK AND START
THE GENERATOR ENGINE. IF ANY BAHERY HAS
DISCHARGED, REMOVE IT FROM THE VEHICLE
FOR RECHARGING.
MAJOR SERVICE MANUAL
To obtain a service manual for your generator, order it from
your dealer/distributor or contact the factory. Be sure to iden
tify
your unit’s MODEL NUMBER and SERIAL NUMBER.
DRIVE BELT
The engine drives the generator rotor by means of a pulley
and drive belt arrangement. The drive belt and pulleys are
warranted for the life of the generator. Drive belt tension was
properly adjusted before the unit was shipped form the fac
tory. If you suspect that drive belt tension is incorrect, contact
an autorized service facility.
EXERCISING THE GENERATOR
Generac recommends that you start and operate the gener
ator at least once every seven days. Let the unit run for at
least 30 minutes to “exercise” the engine.
OUT OF SERVICE PROTEQION
If you cannot exercise the generator every seven days and it
is to be out of service longer than 30 days, prepare the gen
erator for storage as follows;
• Start the engine and let it warm up.
• While the engine is still warm from running, drain the oil com
pletely. Refill crankcase with recommended oil. See
“Specifications.”
• Attach a tag to the engine indicating the viscosity and clas
sification of the oil in the crankcase.
• Remove spark plugs and add about 1/2 ounce (15ml) of
clean, fresh engine oil into spark plug threaded openings.
Crank engine several times to distribute oil, then install and
tighten spark plugs.
• Remove the battery and store in a cool, dry room on a
wooden board. Never store the battery on any concrete or
earthen floor.
• Clean and wipe the entire generator.
RETURN UNIT TO SERVICE
AFTER STORAGE
To return the unit to service after storage, proceed as follows:
• Check tag on engine for oil viscosity and classification.
Verify that the correct recommended oil is used in engine.
If necessary, drain and refill with proper oil.
• Check battery. Fill all cells to the proper level with distilled
water. DO NOT USE TAP WATER IN THE BATTERY.
Recharge battery to 100% state of charge, or, if defective,
replace the battery.
• Press the Fuel Pump Primer switch and hold it for about 30
seconds to activate the automatic shut-off function.
• Turn OFF all electrical loads, then start the engine.
• Let engine warm up.
• Apply electrical loads to at least 50% of the unit’s rated
wattage capacity.
• When engine is thoroughly warmed up, shut it down.
THE GENERATOR IS NOW READY FOR SERVICE.