Gas supply and piping, Alternate btuh input ratings (usa only), Supply pressure – Sears 9MPD User Manual
Page 30: Gas supply pressure, Manifold gas pressure adjustment
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

5. Gas Supply and Piping
CARBON
MONOXIDE
POISONING,
FIRE
AND
EXPLO
SION HAZARD
Models
designated
for
Natural
Gas
are
to
be
used
with
Natural
Gas
Only,
unless
properly
converted
to use with LP gas.
Furnace operating with the wrong fuel result in death,
personal injury and/or property damage.
NOTE: The rating plate is stamped with the model number, gas
type and gas input rating. In addition, models manufactured for
sale in Canada have orifice size information stamped on the rat
ing plate.
Alternate BTUH Input Ratings (USA Only)
The input rating of these furnaces can be changed from the stan
dard input rating to the alternate input rating shown in
Table 5,
by
changing the main burner orifices. NOTE: The input rating ot
80,000 BTUH models cannot be changed from the standard in
put. Changing of burner orifices MUST be done by a qualified ser
vice technician. See section on changing orifices or following
page.
Table .5
Alternate Input Ratings, USA ONLY.
BTUH
Standard
Rating
BTUH
Alternate
Rating
Natural
Gas
Orifice
LP
Gas
Orifice
50,000
40,000
#44
#55
75,000
60,000
#44
#55
100,000
80,000
#44
#55
125,000
100,000
#44
#55
Supply Pressure
FIRE HAZARD
Failure
to
properly
set
input
pressure
can
result
in
death, personal injury and/or property damage.
Do NOT set input rating above that shown on rating
plate.
1. Supply pressure can be checked using the Vg" NPT port
on the supply side of the gas valve.
2.
Gas input to burners
MUST NOT
exceed the rated input
shown on rating plate.
3. Do
NOT
allowminimumgassupply pressure to vary down
ward. Doing so will decrease Input to furnace. Refer to
Table 6
for normal gas supply and manifold pressures.
Table 6
Gas Pressures Below 2000'
Gas
Type
Supply Pressure
Manifold
Pressure
Recommended
Max.
Min.
Natural
7"
14”
4.5"
3.5"
LP
11”
14”
11”
10"
Important Note:
•
With Propane gas, the rated input is obtained when the
BTU content is 2,500 BTU per cubic foot and manifold
pressure set at 10" W.C.
•
If Propane gas has a different BTU content, orifices
MUST be changed by licensed Propane installer.
• Measured input can NOT exceed rated input.
•
Any major change in gas flow requires changing burn
er orifice size.
Gas Supply Pressure
Gas supply pressure should be within minimum and maximum
values listed on rating plate. Pressures are usually set by gas sup
pliers.
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners oper
ating.
FIRE OR EXPLOSION HAZARD
Failure to turn OFF gas at shut off before connecting
manometer can result in death, personal injury and/or
property damage.
Turn OFF gas at shut off before connecting manometer.
1. Remove the burner compartment door.
2.
With gas
OFF,
connect manometer to tapped opening on
gas valve. Use manometer with a 0 to 15" water column
range.
3. Turn gas
ON
and remove adjustment screw cover on gas
valve. Turn counterclockwise to decrease pressure and
clockwise to increase.
4.
For altitudes up to 2000', set pressure to value shown In
Table 6,
± 0.3' water column.
5.
Connect manometer to the tapped opening on the outlet
side of gas valve. Use manometer with a 0-15 ' min. water
column range.
6
.
Turn gas
ON,
fire the furnace and remove adjustment
screw cover on gas valve.
7.
Turn counterclockwise to decrease pressure and clock
wise to increase.
8
.
SetpressuretovalueshowninTable
6.
Refer to
Important
Notes
in Table
6.
Pressure is also listed on furnace rating
plate.
9. When pressure is set, replace adjustment screw cover on
gas valve.
10. Replace the burner compartment door.
О3Ф1
44001
1114
00