Using exterior risers, Vertical termination, Vent termination shielding – Sears 9MPD User Manual
Page 28: Multi vent termination clearances
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

2. Check hole sizes by making sure it is smaller than the cou
plings or elbows that will be installed on the outside. The
couplings or elbows MUST prevent the pipe from being
pushed back through the wall.
3.
Extend vent pipe and combustion air pipe through the wall
^ / 4
" to T" and seal area between pipe and wall.
4.
Install the couplings, nipple and termination elbows as
shown and maintain spacing between vent and combus
tion air piping as indicated in Figure 19 and Figure 20.
A metal shield is recommended 18 " x 18 " min. or 18 " min. diame
ter around the vent termination at the exterior wall to protect the
house exterior materials from flue product or condensation (freez
ing) damage.
Using Exterior Risers
1
.
Install elbows and pipe to form riser as shown in Figure 20.
2. Secure vent pipe to wall with galvanized strap or other rust
resistant material to restrain pipe from moving.
3. Insulate pipe with Armaflex or equivalent moisture resis
tant closed cell foam insulation or Fiberglass insulation if
boxed in and sealed against moisture.
Vertical Termination
1
.
Figure 21 shows the proper installation and clearances for
vertical vent termination. The vertical roof termination
should be sealed with a plumbing roof boot or equivalent
flashing. The inlet ofthe intake pipeand end of the exhaust
vent must be terminated no less than
1
2"
above the roof or
snow accumulation level, and
1 2
" away from a vertical wall
or other protrusion.
2. If the vent system is installed in an existing chimney make
sure clearances shown in Figure 21 are maintained. Hori
zontal section before the termination elbow can be ex
tended on the inlet air to provide necessary clearance.
Vent Termination Shielding
Under certain wind conditions some building materials may be af
fected by flue products expelled in close proximity to unprotected
surfaces. Sealing or shielding oftheexposed surfaces with a cor
rosion resistant material (such as aluminum sheeting) may be re
quired to prevent staining or deterioration. The protective material
should be attached and sealed (if necessary) to the building be
fore attaching the vent terminal.
Multi Vent Termination Clearances
When two (2) or more furnaces are vented near each other, each
furnace must be individually vented.
Two (2) vent terminations may be installed as shown in
Figure 22, Figure 23, Figure 24, Figure 25, Figure 26 and
Figure 27, but the next vent termination must be at least 36" away
from first 2 terminations. It is important that vent terminations be
made as shown to avoid recirculation of flue gases.
[
2
^
44001
1114
00