Optional Wiring Connections - 240 Volt Connector Plug
A
DANGER
All wiring connections should be done by a QUALIFIED electrician. Improper or unauthor
ized wiring connections are not only dangerous, but may damage equipment. Wire gauge
sizes must be large enough to handle the maximum amperage load. All applicable elec
trical codes must be complied with.________________
A 240 volt, 4-prong, 20 amp connector plug is
included
with
the
alternator,
if
additional
plugs are required, refer to REPAIR PARTS
section of Owner’s Manual. The 240 volt
outlet will supply both 120 volts a-c and 240
volts a-c, as shown above, when a 4-wire cable
is connected to the connector plug.
One method of connecting a 4-wire cable to
the connector plug, is to terminate the cable
at a connection box. See illustration above.
When a Stand-By kit is ordered, a 4-wire cord
set
is
inciuded
(see
INSTALLATION
OF
STAND-BY POWER SYSTEMS, page 4).
Optional Wiring Connections - 1 2 0 Volt, 30 Amp Connector Plug
A 120 volt, 3-prong, 30 amp connector plug is
included
with
the
alternator.
If
additional
plugs are required, refer to REPAIR PARTS
section of manual. A 3-wire cable must be pur
chased and connected to the plug as shown
above.
One method of connecting a 3-wire cable is to
terminate the cable at an outlet box, as shown
above
11