beautypg.com

Fig. 4 — gas pipe layout, A warning, 58ed,pb horizontal gas-fired furnaces – Carrier 580PB User Manual

Page 5: Step 6 — connect gas piping, Table 5 — gas pipe sizing (cu ft of gas per hour)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HEATING A COOLING

58ED,PB

Horizontal Gas-Fired Furnaces

MASONRY CHIMNEY — This furnace can be vented

into an existing masonry chimney. Normal connections
to a chimney are made using single wall pipe; however,

single wall pipe is not approved to pass through any attic,
inside wall or concealed space or through any floor. For
further information, consult venting section of National
Fuel Gas Code.
TYPE B-1 VENT — The furnace is also approved for
use with a Type B-1 vent that terminates through the roof

(horizontal venting through an outside wall is not
approved). The vent must be terminated with a listed

cap or roof assembly. This venting must be installed in
accordance with the vent manufacturer’s instructions
and be in accordance with all local codes.

ATTIC INSTALLATION — Attic and/or National Fuel
Gas installations require the use of Type B or Type L vent
material The following requirements are provided for
venting system;

1. Ensure the chimney flue is clear of any dirt or debris.

2. Ensure the chimney is not serving an open fireplace.
3. Never reduce the pipe size below the outlet size of

the furnace.

GAS

SUPPLY

note

:

LOCATE MANUAL SHUTOFF VALVE AS REQUIRED
BY THE LOCAL AUTHORITY OR CODE IN THE
ABSENCE OF SUCH A CODE, LOCATE THE
MANUAL MAIN

FROM THE FLOOR

FIELD SUPPLIED MAIN
MANUAL SHUTOFF VALVE
(SEE NOTE)

FURNACE
GAS VALVE -

GAS

SUPPLY

CD

Tl

r

)

r'l

L

j

PIPE CAP MINIMUM OF I IN. FROM

FLOOR TO PERMIT REMOVAL

GAS PIPE LAYOUT AFTER REVERSING COMPONENTS

Fig. 4 — Gas Pipe Layout

4. All pipe should be supported using the proper clamps

and/ or straps

5. All horizontal runs of pipe must have an upward

slope of 1/4 in. per foot.

6. All runs of pipe should be as short as possible with

as few turns as possible.

7. Seams must be tightly joined and checked for leaks.
8 The flue pipe must not extend into the chimney,

but be flush with the inside chimney wall.

9. The chimney or gas vent must extend 3 ft above the

highest point where it passes through a roof of a
building and at least 2 ft higher than any portion of a
building within a horizontal distance of 10 feet. It
shall also extend at least 5 ft above the highest

connected equipment flue collar.

10 Check local codes for any variance.

Step 6 — Connect Gas Piping

— Install gas piping

to provide a supply of gas sufficient to meet the maximum
demand without undue loss of pressure between the gas
meter and the furnace. The gas line to the furnace should
be a separate line direct from the meter, unless the
existing gas line is of ample capacity. Refer to Table 5
for sizing gas piping.

Use a joint compound (pipe dope) resistant to the

action of liquefied petroleum gases or to any other
chemical constituents of the gases to be conducted
through the piping.

Before any system of gas piping is finally put into

service, it should be carefully tested to determine if it is
gas tight. The piping must withstand a pressure of 6 in. Hg
for a period of 10 minutes or as required by local
authority.

A WARNING

The furnace and its individual shutoff valve must be
disconnected from the gas supply system during any
pressure testing of that system at test pressures in
excess of 1 / 2 psig. The furnace must be isolated from
the gas supply piping system at pressures equal to or

less than 1/2 psig.

The recommended method for installing the gas piping

to the furnace is shown in Fig. 4. Also shown is correct
piping if the gas valve and controls have been reversed
in the field.

Table 5 — Gas Pipe Sizing (Cu Ft of Gas per Hour)'*

DIAMETER OF PIPE — IPS (in.)

PIPE (ft)

Vr

%

1

IV

4

IV

2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

890

40

63

130

245

500

760

50

115

215

440

670

75

93

175

360

545

100

79

150

305

460

150

_

64

120

250

380

* Based on gas pressures of 0 5 psig or less and pressure drop of

0 3 in wg and 0 60 specific gravity gas

Manufacturer reserves the right to discontinue, or change at any time, specitications or designs without notice and without incurring obligations.

Book|1 |4

PC101

Catalog No 535-834

PrintedinUSA

Form 58ED.PB-1SI

Pg5

6-85

Replaces; 58PB-1 SI

For replacement items use Carrier Specified Parts

Tab l6a|8a

This manual is related to the following products: