HEATING & COOLING

58ED,PB

Horizontal Gas-Fired Furnaces

LOCATION OF SHUTTER
LOCKING SCREW

SHUTTER ADJUSTING TAB

NOTE; LOOSEN LOCKING SCREW BEFORE

ADJUSTING

SHUTTER.

RETIGHTEN

SCREW

AFTER FINAL ADJUSTMENTS ARE MADE.

Fig. 14 — Air Shutter Adjustment

Manifold Pressure Adjustment

— For natural

gas, best results are obtained with a manifold pressure of
3.0 in. to 3.5 in. wg. Remove pressure tap pipe plug from
the gas valve and connect to a water manometer. Measure
gas pressure with the furnace on.

Turn regulator adjusting screw in to increase pressure,

or out to decrease pressure.

For LP gases, a 10 in. wg pressure is required. Input

rate must be maintained at ± 2%.

Fan Adjustment Check

— This furnace is equipped

with a 3-speed direct drive motor to deliver a temperature
rise within the range specified on the rating plate, between
the return and supply plenums at the external duct static
pressure noted on the AGA rating plate. Consult the
wiring diagram for speed changes on the direct drive
motor. Adjust fan speed so that temperature rise is within
rating plate specifications.

Fan and Limit Control Check

— After the furnace

has been operating for at least 15 minutes, restrict the
return air supply by blocking the filters or closing the
return air registers and allow the furnace to shut down on
high limit. The fan must continue to run. Remove the
restriction and the burner should come on in a few
minutes.

The operational checkout is now complete. Be sure to

adjust the thermostat to the desired setting and inform
the owner how to operate the furnace system before
leaving the jobsite.

Stopping the Furnace

— Follow these procedures to

shut down the furnace for the summer, if required.

1. Disconnect electrical power to all accessories.

2. To shut down main burner, turn gas cock dial clock­

wise to OFF position

3. (Standing pilot models only): To shut down both

pilot and main burner, depress dial and turn clockwise
to OFF position

4. Turn off all electrical power to furnace.

5. Turn off water supply to humidifier, if so equipped.

Fig. 15 — Burner Flames

SERVICE AND MAINTENANCE

A CAUTION

The ability to properly perform maintenance on this

equipment requires certain mechanical skills and
tools. If you are at all uncertain, contact your Carrier
dealer for qualified maintenance and service.

A WARNING

Turn off all gas and electrical power to furnace

before performing any maintenance or service on
unit. Failure to take this precaution may result in
personal injury due to electrical shock or uncon­
trolled gas leakage.

NOTE; Furnace is equipped with a blower door switch
which cuts electric power when blower door is removed.

Air Filter

— In order to aequaint the user of the furnace

with proper procedure for inspecting and cleaning the

filter, the installer should instruct the user to locate,
remove, clean and replace the furnace filter(s).
NOTE: If furnace is equipped with accessory filter rack,

refer to section on page 11.

A

CAUTION

Personal injury or property damage may result if

furnace is operated with the blower compartment
door removed. A lack of adequate combustion air

may cause the main burner flame to be drawn out of

the furnace unless blower compartment door is

secured.

After inspecting or replacing the filter, be sure that

the blower compartment door is securely fastened in
place. Never operate the furnace without a filter.

Lubricating Motors

— Direct drive motor and

blower assemblies are factory lubricated and normally
do not require oiling.