beautypg.com

A caution, A warning – Carrier 58DHL User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Fig. 13—Amp Draw Check With Ammeter

correspond to that specified on the unit rating plate. Also,

check to be sure that the service provided by the utility is

sufficient to handle the additional load imposed by this

equipment. Refer to the unit rating plate for equipment elec­

trical requirements.

A CAUTION

Do not connect aluminum wire between disconnect

switch and furnace.

See Fig. 15 for wiring diagram showing the proper field

high- and low-voltage wiring. Make all electrical connections

in accordance with the National Electrical Code and any

local codes or ordinances that might apply.

“A F

Fig. 14—Blower Control Center

assise

Use a separate fused branch electrical circuit containing a

properly sized fuse or HACR-type circuit breaker for this

furnace. A disconnecting means must be located within

sight of, and readily accessible to, the furnace. The blower

door switch may be acceptable in some areas as a discon­

necting means.

A WARNING

The cabinet must have an uninterrupted or unbroken

ground according to National Electrical Code, ANSI/

NFPA 70-1987, or local codes to nnniinize personal

injury if an electrical fault should occur. This may con­

sist of electrical wire or conduit approved for electrical

ground when installed in accordance with existing elec­

trical codes. Do not use gas piping as an electrical

ground. A failure to adhere to this warning can result in

an electrical shock, fire, or death.

If hne-voltage wiring to the unit is encased in a nonmetaUic

sheath, connect the incoming ground wire to the groimding

wire inside the furnace J-box. If metaUic conduit is used, it

will serve as the ground.

B. Low-Voltage Wiring

NOTE:

When instaUing a Carrier thermostat P/N TSTOl

and relay system P/N TSROl, follow the instructions pack­

aged with the thermostat and relay for installation

procedures.

Make field low-voltage connections at the low-voltage termi­

nal strip. See Fig. 15.

NOTE:

When the furnace is instaRed in the horizontal posi­

tion with RH discharge air, low-voltage wire connections

can be made easier by removing the two control box mount­

ing screws and letting the control box turn so that the low-

voltage screw terminals are visible. Be sure to reinstall the

control box after the connections are made.

NOTE:

Use AWG No. 18 “color-coded” copper thermostat

wire for lengths up to 100 ft. Above 100 ft, use AWG No. 16

wire.

IMPORTANT:

The thermostat heat anticipation must be

set to match the amp draw of the gas valve and electrical

components in the R-W circuit. Accurate amp draw read­

ings can be obtained at thermostat subbase terminals R &

W. Fig. 13 illustrates an easy method of obtaining the

actual amp draw. The amp reading should be taken after the

blower motor has started.

The room thermostat should be located where it will be in

the natural circulation path of room air. Avoid locations

where the thermostat would be exposed to cold-air infiltra­

tion, drafts from windows, doors, or other openings leading

Fig. 15—Heating and Cooling Application Wiring Diagram

A78461