A caution, A warning – Carrier 58DX User Manual
Page 3
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
------------------ FIELD 24-VOLT WIRING
TERMINAL BLOCK
AS SUPPLIED, MUST BE REPLACED, USE
SAME TYPE OR EQUIVALENT WIRE.
A87502
Fig. 6—Heating and Cooiing Application Wiring Diagram
3. Assemble and install downflow subbase per instruc
tions packaged with subbase.
4. When completed, downflow subbase, plenum, and fur
nace (or coil casing when used) should be installed as
shown in Fig. 4.
VII.
ELECTRICAL CONNECTIONS
A. 115-Volt Wiring
iM PORT ANT:
Before proceeding with the electrical connec
tions, make certain that voltage, frequency, and phase cor
respond to that specified on the unit rating plate and Table
3. Also, check to be sure that the service provided by the
utility is sufficient to handle the load imposed by this equip
ment. Refer to Table 3 for the equipment electrical
specifications.
Table 3—Electrical Data
Volts-
Operating
Max.
Min.
Max. Wire
Max. Fusef or
SIZE
Hertz-
Voltage Range
Unit
Wire
Length
HACR-Type
Phase
Max*
Min*
Amps
Size
Feett
Ckt Bkr Amps
040
115—60—1
127
104
8.7
14
41
15
060
115—60—1
127
104
8.2
14
42
15
080
115—60—1
127
104
10.1
14
36
15
100
115—60—1
127
104
13.6
12
42
20
»Permissible limits of the voltage range at which the unit will operate sat
isfactorily.
fTime-delay fuse is recommended.
^Length shown is as measured one way along wire path between unit
and service panel for maximum 2% voltage drop.
A CAUTION
Do not connect aluminum wire between the disconnect
switch and the furnace.
See Fig. 6 for a wiring diagram showing the proper field
115- and 24-volt wiring. Be sure field wiring complies with
the National Electric Code and any local codes or ordnances
that may apply. Voltage to the furnace must be within the
limits shown in Table 3. Contact your local power company
for correction of improper voltage.
NOTE;
Operation of unit on improper line voltage consti
tutes abuse and could affect unit reliability. Do not install
the furnace in a system where voltage may fluctuate above
or below permissible limits.
Use a separate fused branch electrical circuit containing the
properly sized time-delay fuse or HACR-type circuit breaker
for this furnace. See Table 3 for fuse and wire specifications.
A disconnecting means must be located within sight of, and
readily accessible to, the furnace. The blower door switch
may be acceptable in some areas as a disconnecting means.
Line voltage must enter the auxiliary J-box on the right-
hand side of the furnace.
A WARNING
The cabinet must have an uninterrupted or unbroken
ground according to National Electrical Code. ANSI/
NFPA 70-1987, or local codes to minimize personal
injury if an electrical fault should occur. This may con
sist of electrical wire or conduit approved for electrical
ground when installed in accordance with existing elec
trical codes. Do not use gas piping as an electrical
ground. A failure to adhere to this warning can result in
an electrical shock, fire, or death.
Table 4—Ratings and Performance
SIZE
input
Btuh*
Indoor
Capacity
Btuht
ICS»*
Capacity
Btuht
Temperature
Rise
Range
Heating
Cooling
Motor
HP & Type
Approx
Shipping
Weight
Ext Static
Pressure
Cfm
Ext Static
Pressure
Cfm
040
44,000
40,000
40,000
20—50
0.10
1335
0.5
1265
1/3 PSC
179
060
66,000
60,000
60,000
40—70
0.12
1275
0.5
1170
1/3 PSC
187
080
88,000
81,000
80,000
40—70
0.15
1590
0.5
1565
1/2 PSC
202
100
110,000
101,000
100,000
40—70
0.20
2000
0.5
2035
3/4 PSC
241
*Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 feet, reduce ratings 4% for each 1000 ft above sea level.
tDetermined by U.S. Government tests.
»»Isolated combustion system; GAMA non-weatherized.