HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field- 
supplied, waterproof disconnect switch mounted at, or 
within sight from the unit. Refer to the unit rating plate 
(Fig. 4) for meiximum over-current device size and minimum 
circuit amps (ampacity) for wire sizing.
The field-supplied disconnect switch box may be mounted 
on the unit over the high-voltage inlet hole in the control 
corner panel. See Figs. 2 and 3.
Proceed as follows to complete the high-voltage connections 
to the unit:
1. Connect ground lead to chassis ground connection
when using separate ground wire.
2. Run high voltage leads into unit through inlet hole in
control box post, and to contactor through the hole in 
the bottom of control box. The high voltage leads 
should remain in conduit until entering control box and 
a watertight termination should be made at bottom of 
control box.
SPECIAL PROCEDURES FOR 208-V OPERATION
A WARNING
Make sure that the power supply to the unit is switched 
OFF before making any wiring changes. Electrical 
shock can cause personal injury or death.
For operation of 208 volts, disconnect the yellow 
transformer-primary lead from the contactor. See the unit 
wiring label. Remove the tape and cover from the termined 
on the end of the blue tremsformer-primeiry lead. Save the 
cover. Connect the blue lead to the contactor terminal from 
which the yellow lead was disconnected.
Using the cover removed from the blue lead, insulate the 
loose terminal on the yellow lead. Wrap the cover with elec
trical tape so that the metal terminal cannot be shorted.
Indoor blower motor speed taps should be changed for 208V 
operation on 208/230v rated units. Interchange motor lead 
at blower motor. See “Start-up and Adjustments” section 
(page 9) and unit wiring label.
CONTROL VOLTAGE CONNECTIONS
Locate the room thermostat on an inside wall in the space to 
be conditioned where it will not be subjected to either a cool
ing or heating source or direct exposure to sunlight. Mount 
the thermostat 4 to 5 ft above the floor.
Use No. 18 AWG color-coded, insulated (35 C minimum) 
wires to make the control voltage connections between the 
thermostat and the unit. If the thermostat is located more 
than 100 ft from the unit (as measured along the control 
voltage wires), use No. 16 AWG color-coded, insulated (35 C
minimum) wires.
A grommeted control voltage inlet hole is located in the 
panel adjacent to the control access panel. See Figs. 2 and 3. 
Run the low-voltage leads from the thermostat, through the 
inlet hole, and to the control voltage terminals. Connect the 
thermostat leads to the terminals as shown in Fig. 10.
HEAT ANTICIPATOR SETTING
Factory thermostats have fixed heat anticipator settings. 
No adjustment is required.
CIRCUIT BREAKER
Unit has manual reset circuit breaker which is located in the 
low-voltage wiring box adjacent to low-voltage terminal 
board. If unit fails to operate, first check breaker for tripped
position. If breaker is tripped, re-set and try to start unit. If 
breaker continues to trip there is a problem in the low- 
voltage electrical circuit (electrical short, ground, or trems- 
former overload). Correct the condition and check for nor
mal unit operation.
PREPARING UNIT FOR START-UP
A WARNING
Failure to observe the following warnings could result
in serious personal injury:
1. Follow recognized safety practices and wear protec
tive goggles when checking or servicing refrigerant 
system.
2. Do not operate compressor or provide any electric
power to unit unless compressor termined cover is in 
place and secured.
3. Do not remove compressor terminal cover until edl
electrical sources have been disconnected.
4. Relieve all pressure from system before touching or
disturbing anything inside compressor termined box 
if refrigerant leak is suspected eiround terminals.
5. Never attempt to repair soldered connection while
refrigerant system is under pressure.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure. To 
remove a component, wear protective goggles and 
proceed as follows:
a. Relieve all pressure from system.
b. Cut component connecting tubing with tubing
cutter and remove component from unit.
c. Ceirefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch 
flame.
PRESTARTUP PROCEDURES
Proceed as follows to inspect and prepare the unit for initial 
startup:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU
TION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a 
refrigerant leak. Leeik-test all refrigerant tubing 
connections using electronic leak detector, halide 
torch, or liquid-soap solution. If refrigerant leak 
is detected, see “Refrigerant Leaks” section on 
page 9.
c. Inspect all field- and factory-wiring connections. Be
sure that connections are completed and tight.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that outdoor fan blade is correctly posi
tioned in fan orifice. Blades should clear fan motor
by no more than 1/4 in. The fan blade hub should be
flush with end of motor shaft.
b. Meike sure that air filter(s) is in place.
c. Make sure that condensate drain pan and trap are
filled with water to ensure proper drainage.