Table 4—rated airflow and filter sizes – Carrier 50NQ User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 2—Models 50NQ Air Delivery (Cfm) in 208V-Horizontal Fiow Set-up at indicated

Externai Static Pressure & Voltage (Sizes 018, 024,030, 036, 048, 060)

UNIT
SIZE

VOLT/PHASE/HZ

MOTOR

SPEED

EXTERNAL STATIC PRESSURE—INCHES W.C.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

018

208/1/60

LOW

788

761

758

734

675

644

600

564

525

MED

1195t

1184t

1160t

1121t

1092t

987t

886

744

724

667

581

HI

1425t

1375t

1359t

1308t

1248t

1139t

1030t

917t

786

702

647

024

208/1/60

LOW

802

787

772

738

702

MED

1211t

1200t

1190t

1169t

1138t

1061t

993t

878

768

HI

1473t

1444t

1418t

1377t

1339t

1260t

1195t

997t

838

750

030

208/1/60

LOW

MED

1225

1220

1211

1177

1166

1105

1040

913

_

HI

1483

1470

1450

1415

1372

1319

1245

1098

891

_

036

208/1/60

LOW

_

MED

1421

1388

1343

1306

1252

1165

1058

_

HI

1882f

1809f

1722t

1644t

1546t

1386

1296

1225

1054

042

208/1/60

LOW

_

_

__

__

MED

1421

1388

1343

1306

1252

HI

1882t

1809t

1722t

1644t

1546T

1386

1296

1225

_

_

048

208/1/60

LOW

1603

1584

1489

__

MED

2035

1985

1923

1851

1771

1678

1497

HI

2304t

2262t

2139t

2046

1940

1815

1687

1462

_

__

060

208/1/60

LOW

MED

2205t

2198t

2190t

2188t

2122t

2084

2020

1943

1863

HI

25811

2538t

2455t

2382t

2305t

2258t

2168t

2084

1992

1893

Tabie 3—Modeis 50NQ Air Deiivery (Cfm) in 230-V Horizontai Fiow Set-Up at indicated

External Static Pressure & Voltage (Sizes 018, 024, 030, 036, 048, 060)

UNIT

SIZE

VOLT/PHASE/HZ

MOTOR

SPEED

EXTERNAL STATIC PRESSURE—INCHES W.C.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

018

230/1/60

LOW

913t

905t

891

848

827

765

699

651

606

575

MED

1366t

1336t

1302

1250t

1201t

1098t

982t

898

776

676

609

HI

1584t

1552t

1467t

1414t

1332t

1256t

1146t

101 Of

825

750

665

024

230/1/60

LOW

950t

935t

926t

900

885

811

733

700

MED

1414t

1399t

1373t

1333t

1289t

1229t

1148t

1015t

811

747

HI

1652t

1614t

1556T

1520t

1440t

1375t

1277t

1098t

876

799

701

030

230/1/60

LOW

937

933

929

919

893

_

MED

1425

1413

1391

1358

1326

1268

1196

1071

875

HI

1670t

1576t

1552t

1533t

1468

1419

1324

1134

920

875

036

230/1/60

LOW

1088

1075

1050

MED

1636t

1599t

1553t

1480

1393

1275

1158

1050

_

HI

2034t

1957t

1846t

1734t

1602T

1571t

1316

1225

1072

042

230/1/60

LOW

_

MED

1636t

1599t

1553t

1480

1393

1275

HI

2034t

1957t

1846t

1734t

1602f

1571t

1316

1225

_

048

230/1/60

LOW

1891

1852

1819

1746

1684

1553

_

__

__

MED

2230t

2155t

2060

1989t

1885

1782

1630

1483

HI

2385t

2304t

2183t

2097

1982

1863

1717

1614

1493

_

060

230/1/60

LOW

2027

2000

1993

1972

1940

1872

MED

2546t

2508t

2448t

2382t

2297t

2234t

2150t

2070

1977

1870

_

HI

2837t

2758t

2652t

2587t

2476t

2392t

2304t

2224t

2089

2003

1872

Air deliveries based on unit dry coil without air filter or optional electrical heaters. Deduct field supplied air filter and electric heater pressure drop to
obtain external static pressure available for ducting. Dashes indicate less than minimum airflow and coil icing may occur.

tAirflow exceeds maximum coil velocity. Condensate may be blown off of coil.

If supplemental electric heaters are used, refer to Table 5 for minimum air-flows. These airflows will be slightly greater than those required for unit
operation.

Table 4—Rated Airflow and Filter Sizes

Model

50NQ

Size

018300

024300

030300

036300 1 036500 1 036600

042300 1 042500 | 042600

048300 1 048500 | 048600

060300 1 060500 1 060600

Rated Airflow (Cfm)*

675

900

1100

1300

1500

1750

2100

Recommended Min f

Field Supplied

Filter Size

324

432

540

648

756

864

1030

Disposable Type

Cleanableor High-

Capacity

216

288

360

432

504

576

720

♦Rated in accordance with U.S. Government D.O.E. test procedures and/or ARI Standard 210.
tRequired filter areas shown are based on the larger of the ARI-rated cooling or heating airflow at a velocity of 300 ft/min for disposable type or

450 ft/min for high-capacity type.