Table 4—rated airflow and filter sizes – Carrier 50NQ User Manual
Page 11
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Table 2—Models 50NQ Air Delivery (Cfm) in 208V-Horizontal Fiow Set-up at indicated
Externai Static Pressure & Voltage (Sizes 018, 024,030, 036, 048, 060)
UNIT
SIZE
VOLT/PHASE/HZ
MOTOR
SPEED
EXTERNAL STATIC PRESSURE—INCHES W.C.
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
018
208/1/60
LOW
788
761
758
734
675
644
600
564
525
—
—
MED
1195t
1184t
1160t
1121t
1092t
987t
886
744
724
667
581
HI
1425t
1375t
1359t
1308t
1248t
1139t
1030t
917t
786
702
647
024
208/1/60
LOW
802
787
772
738
702
—
—
—
—
—
—
MED
1211t
1200t
1190t
1169t
1138t
1061t
993t
878
768
—
—
HI
1473t
1444t
1418t
1377t
1339t
1260t
1195t
997t
838
750
—
030
208/1/60
LOW
—
—
—
—
—
—
—
—
MED
1225
1220
1211
1177
1166
1105
1040
913
—
_
—
HI
1483
1470
1450
1415
1372
1319
1245
1098
891
_
—
036
208/1/60
LOW
—
—
—
_
—
—
—
—
—
—
MED
1421
1388
1343
1306
1252
1165
1058
_
—
—
—
HI
1882f
1809f
1722t
1644t
1546t
1386
1296
1225
1054
—
—
042
208/1/60
LOW
—
—
—
—
_
—
—
_
__
__
MED
1421
1388
1343
1306
1252
—
—
—
—
—
HI
1882t
1809t
1722t
1644t
1546T
1386
1296
1225
_
_
048
208/1/60
LOW
1603
1584
1489
—
—
—
__
—
—
—
—
MED
2035
1985
1923
1851
1771
1678
1497
—
—
—
HI
2304t
2262t
2139t
2046
1940
1815
1687
1462
_
__
—
060
208/1/60
LOW
—
—
—
—
—
—
—
—
MED
2205t
2198t
2190t
2188t
2122t
2084
2020
1943
1863
—
—
HI
25811
2538t
2455t
2382t
2305t
2258t
2168t
2084
1992
1893
—
Tabie 3—Modeis 50NQ Air Deiivery (Cfm) in 230-V Horizontai Fiow Set-Up at indicated
External Static Pressure & Voltage (Sizes 018, 024, 030, 036, 048, 060)
UNIT
SIZE
VOLT/PHASE/HZ
MOTOR
SPEED
EXTERNAL STATIC PRESSURE—INCHES W.C.
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
018
230/1/60
LOW
913t
905t
891
848
827
765
699
651
606
575
—
MED
1366t
1336t
1302
1250t
1201t
1098t
982t
898
776
676
609
HI
1584t
1552t
1467t
1414t
1332t
1256t
1146t
101 Of
825
750
665
024
230/1/60
LOW
950t
935t
926t
900
885
811
733
700
—
—
—
MED
1414t
1399t
1373t
1333t
1289t
1229t
1148t
1015t
811
747
—
HI
1652t
1614t
1556T
1520t
1440t
1375t
1277t
1098t
876
799
701
030
230/1/60
LOW
937
933
929
919
893
—
—
—
—
—
_
MED
1425
1413
1391
1358
1326
1268
1196
1071
875
—
—
HI
1670t
1576t
1552t
1533t
1468
1419
1324
1134
920
875
—
036
230/1/60
LOW
1088
1075
1050
—
—
—
—
—
—
MED
1636t
1599t
1553t
1480
1393
1275
1158
1050
—
_
—
HI
2034t
1957t
1846t
1734t
1602T
1571t
1316
1225
1072
—
042
230/1/60
LOW
—
—
—
—
—
—
_
—
MED
1636t
1599t
1553t
1480
1393
1275
—
—
—
—
—
HI
2034t
1957t
1846t
1734t
1602f
1571t
1316
1225
—
_
—
048
230/1/60
LOW
1891
1852
1819
1746
1684
1553
_
__
—
__
—
MED
2230t
2155t
2060
1989t
1885
1782
1630
1483
—
—
—
HI
2385t
2304t
2183t
2097
1982
1863
1717
1614
1493
_
060
230/1/60
LOW
2027
2000
1993
1972
1940
1872
—
—
—
—
—
MED
2546t
2508t
2448t
2382t
2297t
2234t
2150t
2070
1977
1870
_
HI
2837t
2758t
2652t
2587t
2476t
2392t
2304t
2224t
2089
2003
1872
Air deliveries based on unit dry coil without air filter or optional electrical heaters. Deduct field supplied air filter and electric heater pressure drop to
obtain external static pressure available for ducting. Dashes indicate less than minimum airflow and coil icing may occur.
tAirflow exceeds maximum coil velocity. Condensate may be blown off of coil.
If supplemental electric heaters are used, refer to Table 5 for minimum air-flows. These airflows will be slightly greater than those required for unit
operation.
Table 4—Rated Airflow and Filter Sizes
Model
50NQ
Size
018300
024300
030300
036300 1 036500 1 036600
042300 1 042500 | 042600
048300 1 048500 | 048600
060300 1 060500 1 060600
Rated Airflow (Cfm)*
675
900
1100
1300
1500
1750
2100
Recommended Min f
Field Supplied
Filter Size
324
432
540
648
756
864
1030
Disposable Type
Cleanableor High-
Capacity
216
288
360
432
504
576
720
♦Rated in accordance with U.S. Government D.O.E. test procedures and/or ARI Standard 210.
tRequired filter areas shown are based on the larger of the ARI-rated cooling or heating airflow at a velocity of 300 ft/min for disposable type or
450 ft/min for high-capacity type.
11