Fig. 3—dimensional drawing—large cabinet – Carrier 50NQ User Manual
Page 3
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
OPTIONAL SUPPLY-
AIR OPENING
CO
ELECTRICAL
UNIT WT.
CORNER WT. LB./KG.
CENTER OF GRAVITY
UNIT
CHARACTERISTICS
LBS.
KG.
A
B
C
D
E
F
50NQ048
208/230/1/60
450
204
120/54
147/67
101/46
82/37
22-3/4" 577.8
28-1/4" 717.5
50NQ060
208/230/1/60
483
219
128/58
170/77
106/48
80/36
21-1/2" 546.1
27-1/2" 698.5
-OPTIONAL RETURN
AIR OPENING
50NQ REQUIRED CLEARANCES (INCHES)
UNIT TOP.............................................. 48
BLOWER ACCESS PANEL SIDE........................................30
DUCT SIDE OF UNIT...6
MIN.
CONTROL BOX ACCESS SIDE............................................ 30
SIDE OPPOSITE DUCTS........................ 30
BOTTOM OF UNIT.............................................................. 0
NOTES PROVISION MUST BE MADE FOR FRESH AMBIENT AIR TO REACH THE OUTDOOR
COIL WITHOUT RECIRCULATION OF THE AIR FROM THE OUTDOOR FAN DISCHARGE.
1 3/8' DIA.(H.V. ENTRY)-
35.0 (ACCESSORY
ELECTRIC HEAT)
SUPPLY
AIR
DUCT COVER
-CONTROL BOX
ACCESS DOOR
-BLOWER ACCESS
DOOR
3/4 NPT
19.0
DRAIN OUTLET
RIGHT SIDE VIEW
7/8' DIA. K.O.-
2 2 . 2
ALT. ELECT. ENTRY
LEFT SIDE VIEW
Fig. 3—Dimensional Drawing—Large Cabinet