beautypg.com

Performance data (cont), I —i, Total cooler pressure drop (water side) – Carrier 30GB060 User Manual

Page 8: Capacity control steps

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Performance data (cont)

300-

270

240-

210

180-

ISO

120

-

90-

75-

•5

60-1

a.

Ko

UJ

5

(f>

UJ

a.

45-

30-

27

24

21

18-

15-

12

-

9-

TOTAL COOLER PRESSURE DROP (Water Side)

80 90100

600 TOO

1000

COOLER WATER FLOW (6PM)

800

-T—

3

7

10

15

20

COOLER WATER FLOW (L/S)

30

—I-----1—I

40

50 60

CAPACITY CONTROL STEPS

UNIT 30GB060

CONTROL

STEPS

%

DISPLACEMENT

(Approximate)

LOADING SEQUENCE A (Note 1)

LOADING SEQUENCE B (Note 1)

Operating

Operating

No.

of

Compr

No.

of

Cyl

Compressor No.

No.

of

Compr

No.

of

Cyl

Compressor No.

Circuit 1

Circuit 2

Circuit 1

Circuit 2

1

29

1

4

1

*

__

__

Standard

2

43

1

6

1

(One Unloader)

3

72

2

10

1

*

2

4

100.0

2

12

1

2

Accessory Unloader
Added to
Compressor No. 2

1
2

3
4

38

66
85

100

1

2
2
2

4

8

10
12

1

*

1

*

1

*

1

2

*

2
2

1

2
2
2

4

8

10
12

1

*

1
1

2

*

2

*

2

*

2

‘Compressor unloaded.

NOTES:
1. The microprocessor has a random number generator that selects

loading sequence A or B, which in turn determines the com­
pressor circuit that is energized first. This evens out operating

hours on each circuit over an extended period of time

If unit operation is anticipated with system load below minimum
unloaded capacity of chiiler:
a. Consider using 2 smaller units in place of larger unit.
b. Increase

water loop volume

to ensure adequate run time (see

Application Data).