Introduction, Installation, Fig. 2 — water piping – Carrier 50WQ User Manual
Page 2
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

' " Table 1
— Installation Data (s®e Fi^- 1)
•
MODEL 50WQ
1 014
018
022
027 1
033
042
OPER WT (lb)
220
240
260
,^270
f
290
320
DIMENSIONS (ft-in.)
A
1-10-1/8 (Includes Filter Section)
B
1-9-1/8
C
2-10-5/16
2-10-5/16
2-10-5/16
3- 2-5/16 1
3- 2-5/16
3- 2-5/16
D
0- 1-1/2
0- 1-1/2
0- 1-1/2
0- 1-1/2
1
0- 1-1/2
0-3
E
0- 1-5/8
0- 1-5/8
0- 7-5/8
0- 7-5/8
j
0- 7-5/8
0- 5-7/8
SUPPLY DUCT CONN.
(ft-in.) F
0-11-1/4
0-11-1/4
0-11-1/4
0-11-1/4 1
0-11-1/4
0-10-1/4
G
0-10-1/4
0-10-1/4
0-11-7/8
0-11-7/8
1
0-11-7/8
1- 1-5/8
FILfER (1)
Disposable. 1 -in thick
Size (in.)
16x20
_
16x20
16x20
20x20
20x20
f
INTRODUCTION
The 50WQ units are completely self-contained
cooling and heating systems. They are water-to-air
heat pumps designed for indoor installation. They
may be connected into existing duct systems which
are properly sized and designed to handle air
quantity of 350 to 450 cfm per ton of cooling. Re
quired connections include supply air duct, water
supply and return lines, high- and low-voltage
wiring. Factory-supplied air filter is installed in rack
on unit return air section. See Table I for filter size.
Use recommended thermostat and subbase (Table 3)
for proper unit operation.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNIT — Move to final location.
Slide from carton taking special care not to damage
service valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER THESE SYSTEM
REQUIREMENTS before installation:
a. Consult local building codes and National Elec
trical Code (NEC) for special installation
requirements.
b. Consider type of water source. Ensure there is an
adequate supply of water at temperature of 45 F
to 90 F with minimum pressure of 10 psig.
c. Provide sufficient space for water piping, con
densate drain, wiring and servicing unit. See
Fig. 1. When front (external) water piping
connections are used, locate unit so piping does
not block front access panels. (Units installed in
confined areas may have to be removed for major
servicing such as compressor or fan motor
replacement.)
d. Provide a minimum 6-in. clearance between
return air filter and adjacent wall.
e. Mount 50WQ on floor or solid platform so unit is
elevated. Make sure unit is supported from the
bottom. To reduce sound transmission, es
pecially when 50WQ is located in a closet or
utility room having louvered doors, the following
acoustical treatment is recommended; place an
isolation pad under unit. Pad must be same size
as unit base. Construct a 1-in. fiberglass sound
shield in front of unit.
Step 2 — Connect Supply Ductwork
to unit
supply air duct connection flange. Refer to Fig. 1
and Table 1 for connection size and location. If
necessary, refer to Carrier System Design
Manual, Part 2, for system air duct design. When
designing and installing ductwork, consider the
following:
a. Size duct for 350 to 450 cfm per ton of cooling
capacity.
b. Avoid abrupt duct size increases and reductions.
c. Use flexible connectors between ductwork and
unit to prevent transmission of vibration.
BALANCING VALVES
(2) WITH SHUTOFF
3
MIN
w
i
CONDENSATE TRAP
CONDENSATE DRAIN
'WATER
REGULATING
VALVE
SUPPLY RETURN
WATER WATER
► AIRFLOW
i
Fig. 2 — Water Piping
©