Temperature rise, Thermostat heat anticipator check, Limit control safety check – Carrier 58SS/DH User Manual
Page 6: Flow-sensing switch safety check, Draft safeguard switch safety check
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Table 2 — Gas Rate (Cu Ft Per Hr)
SECONDS
SIZE OF
SECONDS
SIZE OF
FOR ONE
TEST DIAL
FOR ONE
TEST DIAL
REVOLU-
1
2
5
REVOLU-
1
2
5
TION
cu ft
cu ft
cu ft
TION
cuft
cu ft
cu ft
10
360
720
1800
50
72
144
360
11
327
655
1636
51
71
141
355
12
300
600
1500
52
69
138
346
13
277
555
1385
53
68
136
340
14
257
514
1286
54
67
133
333
15
240
480
1200
55
65
131
327
16
225
450
1125
56
64
129
321
17
212
424
1059
57
63
126
316
18
200
400
1000
58
62
124
310
19
189
379
947
59
61
122
305
20
180
360
900
60
60
120
300
21
171
343
857
62
58
116
290
22
164
327
818
64
56
112
281
23
157
313
783
66
54
109
273
24
150
300
750
68
53
106
265
25
144
288
720
70
51
103
257
26
138
277
692
72
50
100
250
27
133
267
667
74
48
97
243
28
129
257
643
76
47
95
237
29
124
248
621
78
46
92
231
30
120
240
600
80
45
80
225
31
116
232
581
82
44
78
220
32
113
225
563
84
43
76
214
33
109
218
545
86
42
75
209
34
106
212
529
88
41
74
205
35
103
206
514
90
40
80
200
36
100
200
500
92
39
78
196
37
97
195
486
94
38
75
192
38
95
189
474
96
38
75
188
39
92
185
462
98
37
74
184
40
90
180
450
100
36
72
180
41
88
176
439
102
35
71
178
42
86
172
429
104
35
69
173
43
84
167
419
106
34
68
170
44
82
164
409
108
33
67
167
45
80
160
400
110
33
65
164
46
78
157
391
112
32
64
161
47
76
153
383
116
31
62
155
48
75
150
375
120
30
60
150
49
73
147
367
f. To adjust input rate, remove cap that conceals regu
lator adjustment. Turn adjusting screw counterclock
wise (out) to decrease input When adjusting, DO
NOT change manifold pressure more than 0.3 in. wg.
Make any major adjustment by changing main burner
orifices.
HIGH ALTITUDE— Ratings are approved for altitudes
to 2000 ft for all gases. Ratings for altitudes over 2000 ft
are 4% less for each 1000 ft above sea level. (Furnace must
be derated by changing main burner orifices.)
BURNER AND PILOT FLAMES — The main burner
flame should be elear blue, almost transparent. The pilot
flame should be well defined. See Fig. 6.
Temperature Rise
— Do not exceed the range of
temperature rise specified on the unit rating plate. Deter
mine the air temperature rise as follows:
1. Place duct thermometers in return and supply ducts
as near furnace as possible. Be sure thermometers do
not “see” heat element so that radiant heat will not
affect thermometer readings. This is partieularly
important with straight-run duets.
2. When thermometer readings stabilize, subtract return-
air temperature from supply-air temperature to deter
mine air temperature rise.
3. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
Thermostat Heat Anticipator Check
— Thermo
stat heat anticipator must be set to match amp draw of
gas valve and eleetrical components in R-W circuit.
Accurate amp draw readings can be obtained at thermo
stat subbase terminals R & W. Figure 7 illustrates an easy
method of obtaining actual amp draw. Amp reading
should be taken after blower motor has started.
Fig. 7 — Amp Draw Check with Ammeter
Limit Control Safety Check
— This control shuts
off the combustion control system and energizes the
circulating-air blower motor if the furnace overheats.
The recommended method of checking the limit con
trol is to gradually block off the return air after the
furnace has been operating for at least 5 minutes. As soon
as the limit has proven safe, the return air opening should
be unblocked to permit normal air circulation. By
using this method to check the limit control, it can be
established that the limit is functioning properly and will
“fail-safe” if there is a motor failure. The downflow/
horizontal furnaces have a manual reset limit switch
located on blower housing.
Flow-Sensing Switch Safety Check
— This con
trol proves operation of the draft inducer blower. Check
as follows:
1. Turn off 115-volt power to furnace.
2. Remove control door and disconnect inducer motor
lead wires from inducer printed-circuit board.
3. Turn on 115-volt power to furnaee.
4. Close thermostat switch as if making a normal furnace
start. The pilot should light and then cycle off and on.
If main burners do not light, flow-sensing switch is
functioning properly.
5. Turn off 115-volt power to furnace.
6. Reconnect inducer motor wires, replace control door,
turn on 115-volt power.
Draft Safeguard Switch Safety Check
— This
control permits safe shutdown of furnace during certain
blocked flue conditions. Check as follows:
1. Disconnect power to furnace and remove vent pipe
from furnace outlet collar. Allow time for vent pipe
to cool before removing.
2. Set room thermostat above room temperature and
restore power to furnace.
3. After normal start-up, allow furnace to operate 2
minutes. Block (100%) flue outlet. Furnace should
cycle off within 2 minutes.
4. Reeonneet vent pipe to furnaee outlet collar.
5. Wait 5 minutes. Reset draft safeguard switch.