beautypg.com

Temperature rise, Thermostat heat anticipator check, Limit control safety check – Carrier 58SS/DH User Manual

Page 6: Flow-sensing switch safety check, Draft safeguard switch safety check

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 2 — Gas Rate (Cu Ft Per Hr)

SECONDS

SIZE OF

SECONDS

SIZE OF

FOR ONE

TEST DIAL

FOR ONE

TEST DIAL

REVOLU-

1

2

5

REVOLU-

1

2

5

TION

cu ft

cu ft

cu ft

TION

cuft

cu ft

cu ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

30

120

240

600

80

45

80

225

31

116

232

581

82

44

78

220

32

113

225

563

84

43

76

214

33

109

218

545

86

42

75

209

34

106

212

529

88

41

74

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

75

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45

80

160

400

110

33

65

164

46

78

157

391

112

32

64

161

47

76

153

383

116

31

62

155

48

75

150

375

120

30

60

150

49

73

147

367

f. To adjust input rate, remove cap that conceals regu­

lator adjustment. Turn adjusting screw counterclock­
wise (out) to decrease input When adjusting, DO

NOT change manifold pressure more than 0.3 in. wg.

Make any major adjustment by changing main burner

orifices.

HIGH ALTITUDE— Ratings are approved for altitudes

to 2000 ft for all gases. Ratings for altitudes over 2000 ft
are 4% less for each 1000 ft above sea level. (Furnace must
be derated by changing main burner orifices.)

BURNER AND PILOT FLAMES — The main burner

flame should be elear blue, almost transparent. The pilot
flame should be well defined. See Fig. 6.

Temperature Rise

— Do not exceed the range of

temperature rise specified on the unit rating plate. Deter­

mine the air temperature rise as follows:

1. Place duct thermometers in return and supply ducts

as near furnace as possible. Be sure thermometers do
not “see” heat element so that radiant heat will not
affect thermometer readings. This is partieularly
important with straight-run duets.

2. When thermometer readings stabilize, subtract return-

air temperature from supply-air temperature to deter­
mine air temperature rise.

3. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.

Thermostat Heat Anticipator Check

— Thermo­

stat heat anticipator must be set to match amp draw of
gas valve and eleetrical components in R-W circuit.
Accurate amp draw readings can be obtained at thermo­
stat subbase terminals R & W. Figure 7 illustrates an easy

method of obtaining actual amp draw. Amp reading
should be taken after blower motor has started.

Fig. 7 — Amp Draw Check with Ammeter

Limit Control Safety Check

— This control shuts

off the combustion control system and energizes the
circulating-air blower motor if the furnace overheats.

The recommended method of checking the limit con­

trol is to gradually block off the return air after the
furnace has been operating for at least 5 minutes. As soon
as the limit has proven safe, the return air opening should
be unblocked to permit normal air circulation. By
using this method to check the limit control, it can be
established that the limit is functioning properly and will

“fail-safe” if there is a motor failure. The downflow/

horizontal furnaces have a manual reset limit switch
located on blower housing.

Flow-Sensing Switch Safety Check

— This con­

trol proves operation of the draft inducer blower. Check
as follows:

1. Turn off 115-volt power to furnace.

2. Remove control door and disconnect inducer motor

lead wires from inducer printed-circuit board.

3. Turn on 115-volt power to furnaee.
4. Close thermostat switch as if making a normal furnace

start. The pilot should light and then cycle off and on.

If main burners do not light, flow-sensing switch is

functioning properly.

5. Turn off 115-volt power to furnace.
6. Reconnect inducer motor wires, replace control door,

turn on 115-volt power.

Draft Safeguard Switch Safety Check

— This

control permits safe shutdown of furnace during certain
blocked flue conditions. Check as follows:

1. Disconnect power to furnace and remove vent pipe

from furnace outlet collar. Allow time for vent pipe
to cool before removing.

2. Set room thermostat above room temperature and

restore power to furnace.

3. After normal start-up, allow furnace to operate 2

minutes. Block (100%) flue outlet. Furnace should
cycle off within 2 minutes.

4. Reeonneet vent pipe to furnaee outlet collar.
5. Wait 5 minutes. Reset draft safeguard switch.