beautypg.com

A caution, Fig. 2—accurater (bypass type) components, Table 1—physical data – Carrier 38QN User Manual

Page 2: Table 2—accurater™ chart

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 1—Physical Data

MODEL 38QN

015

018

024

030

036

042

048

060

OPER WT (lb)*

132

151

155

180

195

189

235

270

REFRIGERANT

Control

22

AccuRater'^'^ (Bypass Type)

CONDFAN

Air Discharge
AirQty(Cfm)

Mtr Rpm (60 Hz)

Propeller Type, Direct Drive

Vertical

1850 1 2400 1 3100 1 3800 | 4000 | 5000

830 1 1075 850 | 1075 | 840

CONDCOIL(fins/in.)

Tube Diam

Rows
Refrig Ckts
Face Area (sq ft)

1

Vin.

1

2 2

12.77

6
E-Coil

2 1 3 1

17.33

)

21.88

DIMENSIONS (ft-in.)

Diameter A
Height B

1-9%

2-574

2-7

3-2%

CONNECT, (in. ODF)

Suction

Liquid

Compatible Fitting (Suction) & Flare (Liquid)

% 1 %

%

REFRIG LINES

(in. ODF)

Suction

Liquid

%

%

%

1%t

♦Weight increases slightly with addition of any accessories.
t38QN048-060 require lYs-in. suction line for optimum perform­

ance. A %- X 17s-in. connection adapter accessory (Carrier Part

No. 28AU900061) is available. If a 7s-in. accessory tubing pack­

age is used, expect a slight capacity loss.

When installing, allow sufiBcient space for edrflow clearance,
wiring, refrigerant piping and servicing. Maintain a mini­
mum of 4 ft clearance from obstructions above and 18 in.

around unit (12 in. on valve side). Maintedn a distance of 24

in. between heat pumps. Position so water or ice from roof

or eaves cannot fall directly on unit.

Step 2—Replace Indoor AccuRater™ Piston, if Required-

Check indoor cod piston to see if it matches the required pis­

ton listed in Table 2. If it does not match, replace indoor cod
piston with piston shipped with this outdoor unit (located in

plastic bag taped to valves). See Fig. 2.

Table 2—AccuRater™ Chart

OUTDOOR

UNIT

38QN

OUTDOOR

PISTON

INDOOR

PISTON

015

35

46

018

40

49

024

46

59

030

55

65

036

61

73

042

67

73

048

73

82

060

78

101

FLARE NUT

Step 3—Make Piping Connections—

Outdoor units may be

connected to indoor sections using Carrier accessory tubing

package or field-supplied tubing of refrigerant grade, cor­
rect size and condition (Table 1). For tubing requirements

beyond 50 ft, obtain information from local Carrier

distributor.

Outdoor

Units

Connected

to

Carrier-Approved

Indoor

Units—

Outdoor units contain correct system refrigerant

charge for operation with indoor unit of the same size when
connected by 25 ft of field-supplied or Carrier accessory tub­

ing. Check refrigerant charge for maximum efficiency.

A CAUTION

DO NOT BURY MORE THAN 3 FT OF REFRIGER­
ANT TUBING IN GROUND. If any section of tubing

is buried, there must be a 6-in. vertical rise to valve con­
nections on outdoor unit. If more than the recom­
mended length is buried, refrigerant may migrate to

cooler buried section during extended periods of unit

shutdown. This causes refrigerant slugging and possi­

ble compressor damage at start-up.

CONNECT REFRIGERANT LINES to fittings on unit

suction and liquid service valves (Fig. 1). Liquid service
valve has flare fitting; suction service valve has Compatible

Fitting. Make suction line connection first. Slide flare nut

on liquid line, then flare and connect liquid line. Use a maxi­

mum torque of 15 ft-lb to tighten flare nut. (Do not disas­

semble AccuRater.) Unit Compatible Fitting permits

mechanical or sweat connection as described below.

Models 38QN048,060—When using iVs in. field-supplied

refrigerant suction line, sweat-connect suction line to lYs in.

end of required connection adapter. Be sure to provide a

heat sink at the service valve to prevent damage during

sweating operation. Connect %-in. end of adapter to unit suc­

tion line Compatible Fitting. Connect liquid refrigerant line
to unit. When a 7s-in. field-supplied suction hne is used, pro­

vide a field-supplied %-in. to 7s-in. suction line adapter (not
necessary if 38LS accessory tube is used).

NOTE: Compatible Fitting on outdoor section has alumi­
num plug located beneath compatible nut on suction valve.

Plug keeps contaminants out of Compatible Fitting.

A CAUTION

When removing compatible nut, be careful pressure
build-up does not cause aluminum plug to blow and
cause personal injury. After tubing is hooked up, dis­
card plug.

A87151

Fig. 2—AccuRater (Bypass Type) Components

Mechanical Connection—Mate one set of connections at a
time.

1. Remove nut on Compatible Fitting.

2. Remove plug and be sure 0-ring is in the groove inside

the Compatible Fitting.

3. Cut tubing to correct length. Deburr and size as neces­

sary. Slide nut onto tube.

4. Insert tube into Compatible Fitting until it bottoms.

Tighten nut until it bottoms on shoulder of fitting or
valve. Keep tube bottomed in Compatible Fitting while

tightening nut.

A CAUTION

If undersized, damaged or eUipticaUy-shaped tubing is

used when making Compatible Fitting, leaks may

result.