Carrier 48KHA User Manual
Page 22
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

TROUBLESHOOTING CHART
Table 9 — Heating Service Analysis Chart
SYMPTOM
PROBABLE CAUSE
REMEDY
Pilot will not light
No spark at electrode
Check air gap between electrode tip and pilot burner
Gap should be as shown in Fig. 11 Readjust as
necessary.
Clean moisture or dirt accumulation on electrode
ceramic with cloth.
Cracked ceramic — replace pilot electrode assembly.
Check for loose or broken wiring at and between spark
generator and electrode. Replace wire or tighten con
nection as necessary.
Check fuses or circuit breaker to ensure voltage to unit.
Check 24-volt input to spark generator. If reading is
24 volts, and above steps have been completed, replace
electronic control head portion of control head/gas
valve assembly.
Spark shorting out to main burner
Realign electrode tip away from main burner but main
tain spark gap to pilot burner. See Fig 11.
No gas at pilot burner
Clean pilot orifice.
Check for 24 volts between terminals no. 1 and GR of
gas valve. If reading is 24 volts, and above steps have
been completed, replace gas valve portion of control
head/gas valve assembly.
Burners will not ignite
Water in gas line
Drain — install water trap.
No power to furnace
Check power supply, fuses, wiring, or circuit breaker.
No 24-volt power supply to control
circuit
Check transformer — replace if necessary
Miswired or loose connections
Check all wiring and wirenut connections.
Dirty pilot — yellow flame
Clean pilot orifice
Pilot burning improperly — sharp
blue flame
Replace pilot.
Burned-out heat anticipator in
thermostat
Replace thermostat
No gas at main burners
1. Check for 24 volts between terminals 3 and GR on
control head If reading is 24 volts, replace gas valve
portion of control head/gas valve assembly.
2 If reading is not 24 volts, check flame sensor for
cracked ceramic insulator or shorted sensor cable.
Replace electronic head if sensor circuit is not
defective.
Broken thermostat wire
Run continuity check to locate break.
Inadequate heating
Dirty air filter
Clean or replace filter as necessary
Gas input to furnace too low
Check gas pressure at manifold. Clock gas meter for
input If too low, increase manifold pressure, or replace
with correct orifices
Unit undersized for application
Replace with proper unit — or add additional unit.
Restricted airflow
Clean or replace filter — or remove any restriction.
Blower speed too low ♦,
Use faster speed tap — or install optional blower.
Limit switch cycles main burners
Dirty air filters — clean or replace
Registers closed, restricted ductwork— open or remove
restriction.
Check heat anticipator setting on thermostat — readjust.
Poor flame characteristics
Incomplete combustion results in
Aldehyde odors, (CO), sooting'
flame —- floating flame
Air shutters on burners closed — adjust to soft blue
flame
Check all screws around flue outlets and burner com
partment — tighten
Lack of combustion air See Installation section.
Cracked heat exchanger — replace.
Overfired furnace — reduce input, or change orifices.
Check vent for restriction — clean as required.
Check orifice to burner alignment
22