beautypg.com

Troubleshooting chart – Carrier 50HQ User Manual

Page 13

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

^ TROUBLESHOOTING CHART

PROBLEM

ENTIRE

UNIT

DOES

NOT RUN

CAUSE

Blown fuse

Broken or loose wires

Voltage supply low

Transformer

Thermostat

BLOWER

OPERATES

BUT

COMPRESSOR

DOES NOT

UNIT OFF ON LOW

WATER

TEMPERA­

TURE CONTROL

UNIT

SHORT

CYCLES

Voltage supply low

Thermostat

Wiring

High-pressure controls

Defective capacitor

Seized compressor

Compressor overload open

Compressor motor grounded

Compressor windings open

Low

water

temperature

cutout open (LWTC)

Water

temperature

too

low

on heating

Low

water

temperature

switch

Wiring and controls

Compressor overload

CORRECTION

Replace fuse or reset circuit breaker.

Repiace or tighten the wires.

If voltage is below minimum voltage specified on dataplate, contact
local power company

Check 24-volt transformer for burnout or voltage less than 18 volts

Set thermostat on COOL and lowest temperature setting, unit
should run Set thermostat on HEAT and highest temperature
setting, unit should run. Set fan to ON, fan should run If unit does

not run in all 3 cases, the thermostat could be wired incorrectly,

or faulty To ensure faulty or miswired thermostat, disconnect
thermostat wires at unit and jumper between R, Y, G and W ter­

minals and unit should run

If voltage is below minimum voltage specified on the dataplate,

contact local power company

Check setting, calibration and wiring.

Check for loose or broken wires at compressor, capacitor or

contactor.

___

_____ ______ ___________ _________ _

The unit could be off on the high-pressure cutout control. Reset the

thermostat to OFF After a few minutes, turn to COOL If the com­

pressor runs, unit was off on high pressure (See Problems for
possible causes )

If the unit still fails to run, check for faulty pressure switch by

jumpering the high-pressure control

Check capacitor or Start Thermistor (PTC). If defective, remove,
replace and revise correctly.

Try a start capacitor in parallel with the run capacitor momentarily.

If the compressor starts but the problem reoccurs on starting,

install an auxiliary start kit The hard start kit is comprised of a
recommended start relay and correctly sized capacitor If the

compressor still does not start, replace the compressor

In all cases, an external or internal temperature sensitive com­
pressor overload is used If the compressor dome is too hot to

touch, the overload will not reset until the compressor cools down.

If the compressor is cool and the overload does not reset, there

may be a defective or open overload If the overload is external,

replace the overload, otherwise, replace the compressor

Internal winding grounded to the compressor shell. Replace the
compressor

Check continuity of the compressor windings with anohmmeter If

the windings are open, replace the compressor.

The unit could be off on the LWTC Reset the thermostat to OFF.
After a few minutes, turn to HEAT If the compressor runs, unit was

off on LWTC (see Problems for possible causes).

Lack«,of or inadequate water flow
Entering water too cold.

Scaled or plugged heat exchanger

____ _

Check for defective or improperly calibrated low water temperature
switch

Loose connections in the wiring or the control contactors defective

Defective compressor overload, check and replace if necessary If

the compressor runs too hot, it may be due to the deficient refrig­

erant charge

13

This manual is related to the following products: