As needed, Troubleshooting – Carrier 16JA User Manual
Page 7
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

J."
16
MAX
REASSEMBLY PROCEDURES
and 3.
Refer to Fig. 2
1. Clean all parts.
2.
Replace wearing rings. Use hand pressure
to position new rings.
3. Insert motor end spring and bearing plate
(F-8 Frame Pump only).
4.
Install retaining clip and spring in bear
ing housing.
5. Insert motor end bearing into housing. Should
be a free sliding fit without excessive ra
dial play.
6. Guide the rotor into position.
7. Install end bearing in bearing and wearing
ring housing:
a. Frame F-8 Pumps - Be sure bearing re
tainer pin is in the retainer slot.
b. Frame F-66 Pumps - Be sure bearing re
tainer pin is in the bearing retainer hole.
8.
Install bearing and wearing ring housing.
Tighten cap screws (Frame F-8 pumps), or
stud nuts (Frame F-66 pumps).
9.
Install impeller with impeller key, lock
washer and locking bolt. Bend tabs of washers
over flats of locking bolt heads.
10. Install new 1/32 in. thick EPR gasket by
removing transfer tape from adhesive side
of gasket and positioning gasket on adapter
flange periphery.
11. Assemble motor stator housing and adapter
flange assembly by sliding the housing and
adapter flange assembly into pump casing.
Refer to step 2 of Disassembly Procedures
as to blocking. Install and tighten bolts and
washers. Remove blocking.
12. Connect power supply to stator junction box.
AS NEEDED
Adding Octyl Alcohol
- Octyl alcohol is usually
required when the leaving chilled water tempera
ture starts to rise above design providing the
control set point has not been altered. Since a
rise in leaving chilled water temperature is also
an indication of fouled condensing water tubes,
use the following procedure to determine if
alcohol is required.
PROCEDURE
1. Remove a sample of solution from solution
pump service valve. If solution has no odor
of alcohol (very pungent), then octyl alcohol
should be added.
2. Add alcohol using the procedure outlined in
Carrier Standard Service Techniques, pub
lication SM-16.
3. If alcohol is not required, refer to Trouble
shooting Guide for symptoms of fouled tubes.
Log Sheets
- We recommend that log sheets be
obtained from your Garrier representative and
that readings be taken periodically. They are
used to:
1. Familiarize operator with machine operation.
2. Be of assistance when planning maintenance.
3. Diagnose machine troubles.
Ordering Spare Parts
- Order spare parts from
your nearest Carrier office. To speed up the
process of filling part orders, the following in
formation must accompany the order:
1. Delivery address.
2. Machine size.
3. Machine serial number.
4. Part name, part number and quantity required.
5. Orders for pump parts must show the motor
serial number found on the motor nameplate.
TROUBLESHOOTING
The remedies listed do not represent a series
of corrective procedures. They are merely check
points and possible individual remedies to machine
problems. When the troubleshooting remedies fail
to pinpoint a problem, contact your nearest
Carrier representative for assistance.