beautypg.com

Carrier 38GK User Manual

Page 2

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

INSTALLATION

Mounting Thru-The-Wall

An opening approximately 26-1/2 x 29 in. shall

be made in a wall as close to a nearby cooling coil
as possible. Refer to Fig. 2 to build a frame in a
manner to support the condensing unit.

1. Locate unit with frame into the opening until

the unit extends approximately 1 in. beyond
the outside (finished) wall.

Tilt to the front to allow the water to drain off.

See Fig. 3.

Fasten the unit to the frame with metal straps.

Use flashing under the unit and caulk all edges
to provide a weathertight seal (Fig. 3).

2

.

3.

4.

Fig. 2 — Roughing-ln Supporting Frame

REFRIGERANT LINE SIZING

Selection of Correct Liquid Line

— See Table 3 for

maximum allowable vertical and horizontal dis­

tance between condensing unit and evaporator

using recommended 3/8-in. liquid line.

Selection of the Correct Suction Line Diameter —

To keep line losses at a minimum, refer to Table 4

to select the correct suction line diameters.

Fig. 3 — Flush or Recess Mounting

Table 3 — Recommended Liquid Line Sizes

COND

MAX COND*

UNIT HT (ft)

REFF

UNIT

Above

Below

0-49

Evap

Evap

Liqu

38GK001

40

50

38GK002

40

70

%

38GK003

40

60

Crankcase heater required

*Decrease maximum allowable vertical separation by 20% for

every 10 ft of refrigerant line length over 100 feet At 150 ft of

line length, 0 ft vertical separation is allowed

Table 4 — Recommended Suction Line Diameters

UNIT

MODEL

SUCTION LINE

LENGTH (ft)

SUCTION

LINE

DIAMETER (in.)

0

46

=/

b

38GK001

(All)

47 - 120

%

121 - 150

V

b

*

0 -

28

%

38GK002

(All)

29 -

72

V

b

73 - 150

V

b

*

0 -

19

V

/4

38GK003

201

20 -

52

V

'A

53 - 116

7/*

0 -

18

%

38GK003

301

19 -

48

%

49 - 107

V

b

*

*Field-supplied 7/8-in to 3/4-in adapter is required

NOTE
The above table is based on a line loss of 2 F Longer lengths can
be used in each diameter listed, but the result will be larger line
losses Refer to Carrier, Syracuse Engineering Office for specific
details