beautypg.com

Winco ASCO 300 D Design 30-230 Amp User Manual

Page 4

background image

SECTION 1

INSTALLATION

1--1

Series 300 Automatic Transfer Switches are factory wired

and tested. Installation requires skid removal then

securing the enclosure to the supporting foundation.

Mounting

Refer to the applicable enclosure outline drawing fur-
nished with this switch and mount the Series 300

according to details and instructions shown on diagram.

Protect the automatic transfer switch from

construction grit and metal chips to prevent

malfunction or shortened life of the ATS.

!

Mount the ASCO ATS vertically to a rigid supporting
structure. Level all mounting points by using flat washers

behind the holes to avoid distortion of the switch.

Line Connections

Refer to the Wiring Diagram provided with your Series

300 ATS. All wiring must be made in accordance with the
National Electrical Code and local codes.

De–energize the conductors before making any

line or auxiliary circuitry connections. Be sure

that Normal and Emergency line connections

are in proper phase rotation. Place engine gen-

erator starting control in the OFF position. Make

sure engine generator is not in operation.

It is unnecessary to remove pole covers from the transfer

switch. If you do remove them, reinstall them carefully.

Testing Power Conductors

Do not connect the power conductors to the ASCO
Series 300 transfer switch until they are tested. Installing

power cables in conduit, cable troughs and ceiling-sus-

pended hangers often requires considerable force. The
pulling of cables can damage insulation and stretch or

break the conductor’s strands. For this reason, after the

cables are pulled into position, and before they are
connected, they should be tested to verify that they are

not defective or have been damaged during installation.

Connecting Power Conductors

After the power cables have been tested, connect them to
the appropriate terminal lugs on the transfer switch as

shown on the wiring diagram provided with this Series

300. Make sure the lugs provided are suitable for use with
the cables being installed. Standard terminal lugs are

solderless screw type and will accept the wire sizes listed

on the drawings provided with the Series 300. Be careful
when stripping insulation from the cables; avoid nicking

or ringing the conductor. Remove surface oxides from

cables by cleaning with a wire brush. When aluminum
cable is used, apply joint compound to conductors.

Tighten cable lugs to the torque specified on rating label.

Three cable spacers are included with 150, 200, and 230

ampere transfer switches. When installing power cables,
run the cables through the cable spacers as shown in

Figure 1–1. Position cable spacers within 1½ inches from

lugs.

The cable spacers must be located as shown

for 150, 200, and 230 ampere transfer switches.

!

cable spacer

cable spacers

1 ½ inch approximate

Figure 1–1. Cable spacers for 150, 200, & 230 amp.

transfer switches.