beautypg.com

Winco ASCO 300 D Design 30-230 Amp User Manual

Page 2

background image

Nameplate

The Transfer Switch nameplate includes data for each

specific ASCO Series 300 ATS. Use the ATS only

within the limits shown on this nameplate.

Catalog Number Identification

A typical Catalog Number is shown below with its

elements explained. The example is for a Series 300

ATS with switched neutral, 3 pole, 200 amp, 480 V, in

a Type 1 enclosure:

D 300

B

3

200

N

1

C

Phase Poles

Neutral

C

– overlapping

Amperes

Voltage

Controller

Enclosure

B

– switched

1

– standard

G

– type 4

C

– type 1

F

– type 3R

L

– type 12

3

– three Ø

2

– single Ø

D

220

C

208

E

230

K

415

M

460

J

400

L

440

N

480

F

240

H

380

Q

575

P

550

R

600

150

104

30

70

blank – solid

blank – open type

1X

– if

accessories
ordered

200

*

A

115

B

120

* 200 amp. limited

to 480 volts

terminals for

engine start

contacts

Transfer

Switch

Controller

normal power

connections

emergency power

connections

membrane

controls

200 amp. size in typical enclosure with location of customer connections

terminals for switch

position contacts

load power

connections

cable spacers

(see INSTALLATION)

maintenance

handle

(see

WARNING

under

Manual

Operation)